29
75D2525
DVM Series Direct Vent Gas Fireplace

The gas line connection may be made using 1/2" rigid tubing or an approved ex connector.
Since some municipalities have additional local codes it is always best to consult your local authorities
and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CSA-B149 (1
or 2) Installation Code.
A listed manual shutoff valve must be installed upstream of
the appliance. Union tee and plugged 1/8" NPT pressure
tapping point should be installed upstream of the appliance.
Figure 46
 Install main gas valve (equipment shutoff valve)
in an accessible location. The main gas valve is for turning on
or shutting off the gas to the replace.
Check your building codes for any special requirements for locating equipment shutoff valve to re-
places.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe.
Excess sealant in pipe could result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 46. Locate
sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply
and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment
trap traps moisture and contaminants. This keeps them from going into the burner system gas controls.
If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.

      



 

     

Figure 46

 

3" Minimum
Pipe Nipple
Cap
Figure 46 -
Gas Connection
Tee Joint
Approved Flexible
Gas Line
CSA Design-Certied Equipment Shutoff Valve
with 1/8" NPT Tap*
Sediment Trap/Drip Leg

From Gas Meter
(4.0" w.c. to 10.5" w.c. Pressure)

From External Regulator
(11" w.c. to 13" w.c. Pressure)