Majestic 500DVMNSC Direct Vent Natural Gas Fireplace

User Manual - Page 19

For 500DVMNSC.

PDF File Manual, 68 pages, Read Online | Download pdf file

500DVMNSC photo
Loading ...
Loading ...
Loading ...
19
75D2525
DVM Series Direct Vent Gas Fireplace
36"
(914 mm)
Max.
36"
(914 mm)
Max.

The maximum number of 9 elbows per side wall
installation is three (3). Figure 20
If a 90° elbow is tted directly on top of the replace
ange, the maximum horizontal vent run before the ter-
mination or a vertical rise is 36" (914 mm). Figure 21
A: 10’
B: 7’
7’6”
Figure 22 -
Maximum Vent Run with Elbows
Horizontal 90° Elbow = 3' Reduction
FP1959
A + B = 17' Maximum


             


Figure 20 -
Maximum Three (3) 90° Elbows
Per Installation
3 x 90°
Elbows
3 x 90°
Elbows
FP1176
Figure 21 -
Maximum Horizontal Run with No Rise
FP1177
If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36" (914 mm) Figure 22. This does not apply if the
90° elbows are used to increase or redirect a vertical
rise. Figure 23
 According to the vent graph (Page 15) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20’ (6 m) and if a 90° elbow is required in the
horizontal vent it must be reduced to 17' (5.2 m).
In Figures 22 and 23, Dimension A plus B must not be
greater than 17' (5.2 m).
Figure 23 -
Horizontal Run Reduction
A
B
7’6”
90°
FP2413