Weil-McLain 94 Series 3 Water and steam boilers — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
18 Part No. 550-110-275/1018
Connect steam boiler piping
(continued)
Figure 23 Model 2194 through 2594 steam (2 10-inch risers required)
Drawing legend & notes
(Figure 21 through Figure 24)
1 Riser pipes (one for each supply outlet)
2 Horizontal pipes needed to offset the header to allow for expansion and contraction of the header
3 Steam supply must be located between last riser connection and equalizer elbow
4 Equalizer elbow — full size or reducing
5 Equalizer pipe
6 Close nipple at Hartford loop tee to reduce water hammer potential
7 Condensate return line (gravity or pumped)
8 Pipe to provide 4 inches between water line and top of Hartford loop return nipple
9 Boiler water line — all automatic water level controls must be set to maintain this level
10 Minimum 24 inches between water line and bottom of header
11 Offset tee
Pipe Dimensions
Model Riser A Riser B Header H Equalizer J
2194-2594 10" 10" 12" 4"