5.2 minimum enclosure clearances
A minimum of 6” (62mm) is required to combustibles
from the side of the appliance.
When constructing the enclosure, allow for fi nishing material thickness to maintain clearances.
note:
An optional combustible mantel must be a minimum of 12” (30.5cm) above the top of the faceplate and not to
extend more than 2” (51mm) from the surface. See chart below for further information.
Risk of fi re. Maintain all specifi ed air space clearances to combustibles. Failure to comply with these instructions
may cause a fi re or cause the appliance to overheat. Ensure all clearances (i.e. back, side, top, vent, mantel,
front, etc.) are clearly maintained.
When using paint or lacquer to fi nish the mantel, the paint or lacquer must be heat resistant to prevent
discolouration.
Facing, mantel and/or fi nishing materials must not interfere with air fl ow through air openings, louvres, operation
of louvres or doors or access for service.
5.3 minimum mantel clearances
MANTEL DIMENSIONS
Ref.Height Depth
A
37 3/16” (945mm)
B12” (305mm)2” (51mm)
C14” (356mm)4” (102mm)
D16” (406mm)6” (152mm)
E18” (457mm)8” (203mm)