OPERATION
36k Sequence of Operation
2) Heating overload
c. If Ttube ≥ 136°F, the compressor will run at reduced frequency.
d. If Ttube ≥ 144°F, the compressor will stop and the indoor fan will run at preset speed.
a. If Ttube ≤ 126°F, the unit will return to its original operation state.
b. If Ttube ≥ 131°F, frequency rise is not allowed.
c. If Ttube ≥ 136°F, the compressor will run at reduced frequency.
d. If Ttube ≥ 144°F,the compressor will stop and the indoor fan will blow residue heat and then stop.
Designation of sensors Faults
Indoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for successive 5
seconds
Indoor tube temperature
The sensor is detected to be open-circuited or short-circuited for successive 5
seconds
Outdoor ambient temperature
The sensor is detected to be open-circuited or short-circuited for successive 30
seconds
Outdoor tube temperature
The sensor is detected to be open-circuited or short-circuited for successive 30
seconds, and no detection is performed within 10 minutes after defrost begins.
Exhaust
After the compressor has operated for 3 minutes, the sensor is detected to be
open-circuited or short-circuited for successive 30 seconds.
Overload
After the compressor has operated for 3 minutes, the sensor is detected to be
open-circuited or short-circuited for successive 30 seconds.
Exhaust temperature protection of compressor
If exhaust temperature ≥ 208°F, frequency is not allowed to rise.
If exhaust temperature ≥ 217°F, the compressor will run at reduced frequency.
If exhaust temperature ≥ 230°F, the compressor will stop.
If exhaust temperature ≤ 194°F, the compressor has stayed at stop for at least 3 minutes, the compressor will resume its operation.
Communication fault
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the compressor will
resume its operation. If module protection occurs six times in succession, the compressor will not be started again.
Overload protection
If temperature sensed by the overload sensor is over 239°F, the compressor will stop and the outdoor fan will stop with a time lag of 30
seconds. If temperature is below 203°F, the overload protection will be relieved.
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a timelag of 30 seconds.
When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3 minutes, the compressor will
resume its operation.