Friedrich FSHSW18A3A Single Zone WallMounted Indoor Unit wit

User Manual - Page 132

For FSHSW18A3A. Also, The document are for others Friedrich models: FSHW091, FSHW121, FSHW183, FSHW243, FSHW363

PDF File Manual, 171 pages, Read Online | Download pdf file

FSHSW18A3A photo
Loading ...
Loading ...
Loading ...
132 PB
TROUBLESHOOTING
18-24k Diagnosis of overload and discharge malfunction
Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit)
Main detection point:
Malfunction diagnosis process:
If the electron expansion valve is connected well? Is the expansion valve damaged?
If the refrigerant is leakage?
If the overload protector is damaged?
Connect wire
well with wiring
diagram
Replace EKV
coil of electron
expansion valve
Remove
malfunction?
After the unit
for 20min
de-energized
Remove
malfunction?
The resistance value of
firs t 4 l ea d fo ot an d th e
fif th lead foot is similar,
less than 100
Y
If the wiring terminal FA of electron
expansion is well connected?
Y
N
N
N
If the overload protector SAT
is well connected?
N
Under ambient temperature, test the
resistance of overload protector with ohmic
Y
Replace
overload
protector SAT
N
Y
Replace
Check refrigerant, if there is
leakage, please refer to
specification
control board
AP1
End
Loading ...
Loading ...
Loading ...