Samsung AC078BNPDBC/TC 8.0 HP Floor Standing Inverter

User Manual - Page 67

For AC078BNPDBC/TC. Also, The document are for others Samsung models: AC078BNPDBC

PDF File Manual, 76 pages, Read Online | Download pdf file

AC078BNPDBC/TC photo
Loading ...
Loading ...
Loading ...
67
English
INSTALLATION PARTS
The table below give indication about self diagnostic routine. Some of error code requires activities
exclusively for Authorized Service Center.
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and
INVERTER PCB.
No.
Error
Code
Meaning Remarks
1E108
Error due to repeated address setting(when 2 or
more devices has same address within the network)
Check on repeated indoor unit main
address
2 E121
Error on indoor temperature sensor of indoor
unit(Short or Open)
Indoor unit Room Thermistor Open/
Short
3 E122
Error on EVA IN sensor of indoor unit(Short or Open)
Indoor unit EVA_IN Thermistor Open/
Short
4 E123
Error on EVA OUT sensor of indoor unit(Short or
Open)
Indoor unit EVA_OUT Thermistor Open/
Short
5E153
Error on float switch (2nd detection)
"Indoor unit Float Switch Open/Short
Drain Pump operation Check"
6E154
RPM feedback error of indoor unit
Check on indoor unit indoor Fan
operation
7E162
Outdoor unit EEPROM Read/Write error (H/W) Check Outdoor EEPROM PBA
8E163
Outdoor unit EEPROM Read/Write error (Option) Check Outdoor EEPROM Data
9E198
Error on thermal fuse of indoor unit (Open)
Thermal Fuse Open Check of indoor unit
Terminal Block
10 E201
"Communication error between indoor and outdoor
unit(Installation number setting error repeated
indoor unit address,indoor unit communication cable
error)"
Check indoor quantity setting in outdoor
11 E202
"Communication error between indoor and outdoor
unit(Communication error on all indoor unit, outdoor
unit communication cable error)"
Check electrical connection and setting
between indoor unit and outdoor unit
12 E205
Communication error on all PBA within the outdoor
unit C-Box,communication cable error
-
13 E206
E206-C002 : Fan PBA communication error,
E206-C003 : INV PBA communication error
-
14 E221
Error on outdoor temperature sensor (Short or Open) Check Outdoor sensor Open / Short
15 E231
Error on outdoor COND OUT sensor (Short or Open) Check Cond-Out sensor Open / Short
16 E251
Error on discharge temperature sensor of compressor
1 (Short or Open)
Check Discharge sensor Open / Short
17 E320
Error on OLP sensor (Short or Open) Check OLP sensor Open / Short
18 E346
Error due to operation failure of Fan2 Fan2 error
19 E347
Motor wire of Fan2 is not connected Fan2 error
Troubleshooting
ki]_TXX^ZXjTWWpiptwhjGz{jluUGGG]^ YWYYTW[TW_GGG㝘㤸G`aXYa\X
Loading ...
Loading ...