English
Deciding on where to install the product
INSTALLATION PARTS
3 When air inlet and air outlet of the outdoor unit are blocked
Case 1: Obstacle on exhausting side is higher than the unit.(regardless of the height of obstacle on suction
side)
The upper part of the outdoor unit is not blocked (Unit: mm)
When installing 1 outdoor unit When parallel installing more than 2 outdoor units(*1)
1500 or
more
300 or
more
1500 or
more
300 or
more
300 or
more
1500 or
more
600 or more
600 or more
1500 or
more
300 or
more
The backside block can not be higher than the outdoor unit. If the backside block is higher than the
outdoor unit, arrange the outdoor unit higher than the backside block.
Case 2: Obstacle on exhausting side is lower than the unit.(regardless of the height of obstacle on suction
side)
The upper part of the outdoor unit is not blocked (Unit: mm)
When installing 1 outdoor unit When parallel installing more than 2 outdoor units(*1)
1500 or
more
300 or
more
1500 or
more
300 or
more
300 or
more
1500 or
more
600 or more
600 or more
1500 or
more
300 or
more
The frontside block can not be higher than the outdoor unit. If the frontside block is higher than the
outdoor unit, arrange the outdoor unit higher than the frontside block.
(*1) When installing outdoor units paralleled, more than 600mm gap shall be left.
When front and rear side of the outdoor unit is toward the wall
1500 or more
600 or more
3000 or more