38
English
Installation of the indoor and outdoor unit
INSTALLATION PARTS
Installing indoor unit
1 Open the air inlet grille in the front and unscrew 4 bolts on
the bottom of the product.
2 Remove the wooden palette used for product transport.
3 Install the product on an even floor.
4 bolts
Installing Outdoor unit
WARNING
Make sure to remove the wooden pallet before installing the outdoor unit. If you do not remove the
wooden pallet, there is risk of fire during welding the pipes. If the outdoor unit is installed with wooden
pallet on, and it was used for long period time, wooden palette may break and cause electrical hazard or
high pressure may damage the pipes.
1 Install the outdoor unit 150mm higher than the base ground and install the drain hole to connect the
pipe to the drainage.
2 When the front fan of an outdoor unit is installed in a place where the average snowfall is more than
150mm, the discharge duct should be attached to the outdoor unit.
3 The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
4 It is necessary to install wire mesh or steel bar when outdoor units are installed on a soft foundation.
5 When installing multiple outdoor units at the same place, install the H beam on the base ground. (When
installing a number of outdoor units, you can install it on the base ground.)
6 Install the H beam(150mm x 150mm x t10 : basic specification) or vibration absorption frame to jut out
from the base ground.
7 After installing the H beam, apply corrosion protection.
Installation of the indoor and outdoor unit
ki]_TXX^ZXjTWWpiptwhjGz{jluUGGGZ_ YWYYTW[TW_GGG㝘㤸G`aXYa[^