48
English
Refrigerant piping work
INSTALLATION PARTS
Pipe bending
1 Perform bending of the pipe using the bender which has a
specified bending radius.
2 Be sure to take full care to perform bending of the pipe
successfully at one time. Bending and unbending the pipe
more than twice makes the bending work increasingly
difficult.
3 You may use the spring inserted into the gas pipe instead
of the bender to bend the pipe.
4 When you bend the pipe using the spring, hold the pipe
with both hands to prevent any distortion, and secure a
minimum bending radius over 100mm.
Spring
Connecting the drain hose
Connect the drain hose by inserting the extension
drain hose to the drain connection port tightly.
Insulated the extension drain hose, then fix it with a
cable tie or a tape.
Drain pan
Cable tie
Insulation
Drain hose
Piping material
Vinyl chloride
(inner diameter of Ø16mm)
Insulation Foamed polyethylene