8. Test run
8.1. Before test run
After installation of indoor and outdoor units, and piping and electric wir-
ing work, recheck that the unit is free from leaks of refrigerant, loosened
connections, and incorrect polarity.
Measure an impedance between the power supply terminal block (L, N, )
on the units and the ground with a 500 V Megger and check that it is equal
to or greater than 1.0 MΩ.
7. Installing the grille
Fig. 7-11
7.5. Installing the intake grille (Fig. 7-11)
Perform the procedure that is described in “7.2. Preparing to attach the grille” in
reverse order to install the intake grille and the corner panel.
A
Refrigerant piping of the main unit
B
Drain piping of the main unit
C
Corner panel
* Installation in any position is possible.
D
Position of the levers on the intake grille when sent from the factory.
* Although the clips can be installed in any of four positions.
7.6. Check
Make sure that there is no gap between the unit and the grille, or between the
grille and the surface of the ceiling. If there is any gap between the unit and the
grille, or between the grille and the surface of the ceiling, it may cause dew to
collect.
Make sure that the wires have been securely connected.
8.2. Test run
Refer to the installation manual that comes with each remote controller for de-
tails.
8.3. Self-check
Refer to the installation manual that comes with each remote controller for de-
tails.
RF thermostat is not established.
Errors detected by indoor unit
Wired remote controller
RF thermostat
Symptom Remark
Check code
P1 Intake sensor error
P2 Pipe (TH2) sensor error
P9 Pipe (TH5) sensor error
E6, E7 Indoor/outdoor unit communication error
P4 Drain sensor error
P5 Drain pump error
PA Forced compressor error
P6 Freezing/Overheating safeguard operation
EE Communication error between indoor and outdoor units
P8 Pipe temperature error
E4 Remote controller signal receiving error
Fb Indoor unit control system error (memory error, etc.)
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
RF thermostat
Symptom Remark
Check code
E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
For details, check the LED dis-
play of the outdoor controller
board.
UP Compressor overcurrent interruption
U3, U4 Open/short of outdoor unit thermistors
UF Compressor overcurrent interruption (When compressor locked)
U2 Abnormal high discharging temperature/49C worked/insuf cient refrigerant
U1, Ud Abnormal high pressure (63H worked)/Overheating safeguard operation
U5 Abnormal temperature of heat sink
U8 Outdoor unit fan safeguard stop
U6 Compressor overcurrent interruption/Abnormal of power module
U7 Abnormality of super heat due to low discharge temperature
U9, UH
Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to
main circuit/Current sensor error