5-1. PURGING PROCEDURES AND LEAK TEST
1)
Removeserviceportcapsfromstopvalvesonbothsidesofrefrigerantlines.
(Thestopvalvesarefullyclosedwhenshipped.)Leaveclosed.
2)Connectgaugemanifoldtoportsofstopvalves.
5-4.EXPLANATIONTOTHEUSER
• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousethe
airconditioner(theremotecontroller,removingtheairlters,placingorremov-
ingtheremotecontrollerfromtheremotecontrollerholder,cleaningmethods,
precautionsforoperation,etc.)
• RecommendthattheuserreadtheOPERATINGINSTRUCTIONScarefully.
Stopvalve
forGAS
Stopvalvecap
(Torque15to
22ft-lb,19.6to
29.4N•m,200
to300kgf▪cm)
Vacuumpump(orthe
vacuumpumpwiththe
functiontopreventthe
backow)
Gaugemanifold
valve(forR410A)
Compoundpressure
gauge(forR410A)
–14.7psi[Gauge]
(–0.101Mpa)
Handle
Low
HandleHigh
Adapterfor
preventingthe
backow
Chargehose
(forR410A)
*Close
*Open
Hexagonal
wrench
Precautionswhenusingthe
controlvalve
Whenattachingthecontrolvalve
totheserviceport,valvecoremay
deformorloosenifexcesspressure
isapplied.Thismaycausegasleak.
Serviceport
Chargehose
Body
Close
Open
Controlvalve
A
Whenattachingthecontrolvalvetothe
serviceport,makesurethatthevalve
coreisinclosedposition,andthen
tightenpartA.DonottightenpartA
orturnthebodywhenvalvecoreisin
openposition.
Serviceportcap
(Torque10to13
ft-Ib,13.7to17.7
N•m,140to180
kgf•cm)
*4to5turns
3)Evacuate the system to 4000 microns from both service valves. System
manifoldgaugesmustnotbeusedtomeasurevacuum.Amicrongaugemust
beusedatalltimes.BreakthevacuumwithNitrogen(N2)intothedischarge
servicevalveto0PSIG.
4)Evacuatethesystemto1500microns.BreakthevacuumwithNitrogen(N2)
intothedischargeservicevalveto0PSIG.
5)Evacuatethesystemto500microns.
6)Closegaugemanifoldvalves,stopthepump,andconducta30minuterise
test.
7)Systemshouldhold500micronsforaminimumof1hour.
8)Fullyopenallstopvalvesonbothsidesofgaspipeandliquidpipe.Operating
withoutfullyopeninglowerstheperformanceandthiscausestrouble.
9)Referto 1-3 and charge the prescribed amount of additional refrigerant if
needed.Besuretochargeslowlywithliquidrefrigerant.Otherwisecomposi-
tionoftherefrigerantinthesystemmaybechangedandaffectperformance
oftheairconditioner.
10)Removegaugemanifoldsandreplaceserviceportcapsandtighten.
11)Leaktest
Stopvalve
forLIQUID
5. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Pressuregauge
(forR410A)
Caution:
• Aftertestrunorremotesignalreceptioncheck,turnofftheunitwiththe
E.O.SWortheremotecontrollerbeforeturningoffthepowersupply.Ifthis
procedureisnotperformed,theunitwillautomaticallybeginoperationwhen
powersupplyisresumed.
To the user
• Afterinstallingtheunit,explaintotheuseraboutautorestartfunction.
• Ifautorestartfunctionisunnecessary,itcanbedeactivated.Consultthe
servicerepresentativetodeactivatethefunction.Refertotheservicemanual
fordetails.
5-2. TEST RUN
1)Insertpowersupplyplugintothepoweroutletand/or
turnonthebreaker.
2)PresstheE.O.SWonceforCOOL,andtwiceforHEAT
operation.Testrunwillbeperformedfor30minutes.If
theleftlampoftheoperationindicatorblinksevery0.5
seconds,inspecttheindoor/outdoorunitconnecting
wire(A)formis-wiring.Afterthetestrun,emergency
mode(settemperature75°F[24°C])willstart.
3)Tostopoperation,presstheE.O.SWseveraltimes
untilallLEDlampsturnoff.Refertooperatinginstruc-
tionsfordetails.
Checking the remote (infrared) signal reception
PresstheOFF/ONbuttonontheremotecontroller(12)andlistenforan
audibleindicatorfromtheindoorunit.PresstheOFF/ONbuttonagaintoturn
theairconditioneroff.
• Oncethecompressor stops,therestartpreventivedevice operatessothe
compressorwillnotoperatefor3minutestoprotecttheairconditioner.
5-3. AUTO RESTART FUNCTION
Thisproductisequippedwithanautorestartfunction.Whenthepowersupply
iscutoffduringoperation,suchasduringblackouts,thefunctionautomatically
startsoperationintheprevioussettingoncethepowersupplyisresumed.
(Refertotheoperatinginstructionsfordetails.)
Emergencyoperation
switch(E.O.SW)
6. PUMPING DOWN
Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatrefrigerantisnotreleasedintotheatmosphere.
1)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.
2)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.
3)Closethestopvalveonthegaspipesideoftheoutdoorunitalmostcompletelysothatitcanbeeasilyclosedfullywhenthepressuregaugeshows0psi[Gauge]
(0Mpa).
4)StarttheemergencyCOOLoperation.
TostarttheemergencyoperationinCOOLmode,disconnectthepowersupplyplugand/orturnoffthebreaker.After15seconds,connectthepowersupplyplug
and/orturnonthebreaker,andthenpresstheE.O.SWonce.(TheemergencyCOOLoperationcanbeperformedcontinuouslyforupto30minutes.)
5)
Fullyclosethestopvalveonthegaspipesideoftheoutdoorunitwhenthepressuregaugeshows(
0.1to0psi[Gauge](0.05to0Mpa))
.
6)StoptheemergencyCOOLoperation.
Tostopoperation,presstheE.O.SWseveraltimesuntilallLEDlampsturnoff.Refertooperatinginstructionsfordetails.
WARNING
When pumping down the refrigerant, stop the compressor before dis-
connecting the refrigerant pipes. The compressor may burst if air etc.
get into it.
JG79Y071H02_en.indd 10 2016/01/21 13:20:07