Electrical Connections
Liebert
®
SRC
User Manual 74
6.2 Communication-cable Specifica t ions
Use a 4 conductor, shielded, stranded cable between the outdoor unit and the indoor unit.
Minimum 18-gauge shielded CVVS or CPEVS cable.
•Insulation materials as required by local code.
Rated for continuous exposure of temperatures up to 1
40°F.
Maximum allowable cable length: 984 ft.
•Firmly attach the cable. Provide slack but secure in a way to prevent external forces from being
imparted on the terminal block.
Terminate the cable shield to a grounded surface at the
outdoor unit only.
6.3Communication Cables between the Unit and Contr o lle r
•Field-supplied, 18 gauge, stranded 4-conductor communication cable (shielded).
All insulation material as recommended by local code.
Starting at the outdoor unit, terminate the cable on terminals Internet A and Internet B. Route the cable
as needed between each
device.
NOTE
Always verify that the communication cable is connected to a
communications terminal on the unit. Never apply line-voltage power to the
communication-cable connection. If contact is made, PCBs may be
damaged.
The shield of the communication cable connecting the outdoor unit to the
indoor unit should be grounded only to the outdoor-unit frame.
Tie the shield of each cable segment together using a wire nut at each
indoor unit. Maintain polarity through the communication network.
Never use a common multiple-core communication cable. Each
communications bus must be provided a separate cable (that is, between
the outdoor unit and indoor unit).
MFL67502030 17. 7. 13. 오오 3:05 Page 84