Electrical Connections
Liebert
®
SRC
27launaM resU
6.1 Power-supply/Power-wiring Specifications
Liebert SRC systems operate at 1 , 208 230 V, 60 Hz.Ø
Power-supply wire type and size should be selected based on National Electrical Code and local
codes. Maximum allowable voltage fluctuation ±10% or nameplate rated value. Refer to Figure 6-1 for
wiring guidelines.
Properly ground the indoor and outdoor unit per National Electrical Code and local codes.
Use only copper wiring that is stranded and shielded with the wires separately insulated.
Ground wire should be longer than the common power/communication wires.
Refer to the appropriate circuit and terminal-block diagrams for your model unit.
Always match color codes of each wire and follow wiring diagram.
Figure 6-1 Indoor and Outdoor wiring and communications cable diagram
Best practice dictates using ring or spade terminals to terminate power wiring at the power terminal block,
Figure 6-2.
Figure 6-2 Typical ring terminal
6/16” ± 2/16”
13/16”
GN/YL
Power Wiring, Ground
to Outdoor Unit
Power Wiring, Ground,
Communication Cable
From Outdoor Unit
To Indoor Unit
13/16”
GN/YL
Line Voltage
(208/230V)
GN/YL = (Green, Yellow)
6/16” ± 2/16”
For 9/12K Indoor Units: AWG 14
For 18K Indoor Units: AWG 12
For 9/12/18K Indoor Units: AWG 18
Ring Terminal
Power Wiring
MFL67502030 17. 7. 13. 오오 3:05 Page 82