Operation
95 Liebert
®
SRC™ User Manual
3. Set the cooling setpoint by pressing ,
then adjust the temperature displayed
under Cool-temperature setpoint in the Temperature section of the display by pressing .
4. Set the cooling setpoint by pressing ,
then adjust the temperature displayed
under Heat-temperature setpoint in the
Temperature section of the display by pressing .
8.5.7 Selecting Timed Override
Timed override temporarily overrides the current schedule (occupied/unoccupied).
• Reverts to last occupied schedule in unoccupied override.
• Reverts to last unoccupied schedule in occupied override.
See 8.6.5, Setting Override Time, page 98, to set the duration of the override.
Press for 3 seconds.
Timed
override is enabled.
• To cancel timed override, press for 3 seconds.
Operation reverts to last weekly schedule.
8.5.8 Selecting Set Back
Set Back reverts to the last unoccupied schedule until set-back operation is canceled. If there is no
unoccupied schedule, it returns to the default set-back setting. See 8.6.6, Setting Set-back Temperature,
page 98, to set the set
-back setting.
Press .
Set back is enabled.
• To cancel set back, press .
NOTE
• You cannot changes settings in set-back mode. HL and the lock is
displayed.
• Set back is canceled if a command from another controller is received.