Cool Differential Temp
The minimum difference between the current temperature and
set temperature before the system calls for cool. A smaller
difference means shorter cycle times, whereas a larger
difference results in longer cycle times. The temperature range is
adjustable from 0 to 3 °F (0 to 1.7 °C) in 0.5°F (0.3°C) increments.
On Thermostat:
1. Select Main Menu > Settings > Installation Settings >
Thresholds > Cool Differential Time.
2. Configure the settings as required.
Cool Dissipation Time
The amount of time the fan will run after the cool has been
turned off. Running the fan for a period of time allows for any
cooled air left in the ducts to circulate throughout the home.
The time is adjustable from 0 to 900 seconds. The default value is
30 seconds.
On Thermostat:
1. Select Main Menu > Settings > Installation Settings >
Thresholds > Cool Dissipation Time.
2. Configure the settings as required.
Cool Min On Time
Sets the minimum equipment run time in cool mode: 1 to 20 min
(default is 5 min).
On Thermostat:
1. Select Main Menu > Settings > Installation Settings >
Thresholds > Cool Min On Time.
2. Configure the settings as required.
Compressor Reverse Staging
If enabled, the thermostat will cycle down from the higher
stages so that as it approaches set point it will only be running in
stage 1. The thermostat calculates which stage to start the
HVAC equipment in depending on the indoor and set point
temperature delta. . As the stage 1 temperature delta is
exceeded, the second stage will engage. Once the equipment
has brought the current temperature back to within the heat or
cool differential setting, stage 2 will disengage and stage 1 will
remain running until the set point is reached.
On Thermostat:
1. Select Main Menu > Settings > Installation Settings >
Thresholds > Compressor Reverse Staging.
2. Configure the settings as required.
Compressor Stage 2 Temp Delta
The minimum difference between the current temperature and
the set temperature that will activate the auxiliary heat
(regardless if the maximum run time of the previous stage was
reached). Options are Auto (default) and 1 to 10 °F (0.6 to 5.6
°C).
On Thermostat:
1. Select Main Menu > Settings > Installation Settings >
Thresholds > Compressor Stage 2 Temp Delta.
2. Configure the settings as required.
Compressor Stage 1 Max Runtime
The maximum amount of time stage 1 will run before engaging
the next stage. Options are Auto (default) and 10 to 120
minutes.
On Thermostat:
1. Select Main Menu > Settings > Installation Settings >
Thresholds > Compressor Stage 1 Max Runtime.
2. Configure the settings as required.
Compressor to Aux Temp Delta
The minimum difference between the current temperature and
the set temperature that will activate this stage (regardless if the
maximum run time of the previous stage was reached). Options
are Auto (default), Disabled, and 1 to 10 °F (0.6 to 5.6 °C).
On Thermostat: