Thermometer Testing
To test for thermometer accuracy, use a mixture of crushed ice and water to form a
slush. Place the thermometer bulb in the mixture and check the reading. Thermometer
should read approximately 32
o
F. If not, recalibrate per instructions. Thermometer
testing is a required part of installation to insure against calibration drift that may have
occurred during shipment. Once thermometer calibration is confirmed, the thermometer
bulb should be mounted away from the door opening.
Thermometer Recalibration
Remove the face cover of the analog dial thermometer. The cover will either screw off
or pry off. Take care not to damage the cover during removal.
For lowering the reading, carefully hold the pointer. Insert screwdriver in pointer
slot and slowly turn clockwise a small amount. Adjust to proper setting.
For higher temperature reading, carefully hold the pointer. Insert the screwdriver
in pointer slot and slowly turn counter clockwise a small amount. Adjust to
proper setting.
Carefully reinstall the face of the thermometer.
Scan the QR Code below for the Thermometer Calibration Service Video.