(see wiring diagram, Figure 65, page 59)(continued)
M. 0–10 VDC Remote MODULATION input – OPTIONAL
TerminalBlockP15#5&#6(EVG control module, left side)
1. See illustration at right and Figure65,page59 for details.
2. is illustration also shows how to connect TT or end switch contacts at
INPUT2 and INPUT3 for other uses.
3. Note that using 0–10VDC input replaces INPUT1 for generating a heat
demand. Do not wire any input to INPUT1 as shown at right.
4. Remote modulation requires a 0–10VDC input signal at P15-4/5 as shown
at right.
a. e 0–10VDC input positive connection must be at terminal6 and com-
mon connection at terminal5.
5. Control setup:
a. Many options are available for conguring the control. e following is
a suggested setup that uses factory default settings as much as possible.
b. Default is BASIC in the Contractor menu.
c. If DHW is required, use PRIORITY1 to minimize setup steps.
y Connect the DHW aquastat to INPUT2 or INPUT3 and assign the
input used to PRIORITY1.
y Verify that control settings are suitable for the application, change
if necessary.
d. Use PRIORITY2 for the system to be remote modulated.
y e factory default settings for this priority are best suited for space
heating.
y Assign INPUT1 to the priority chosen. Accept all defaults for IN-
PUT1 — no changes should be necessary during the WIZARD.
y Aer the WIZARD has been completed, go to the ASSIGN INPUTS
menu for INPUT1. Change SOURCE to 0–10V (default setting is
TT1). See page78 for ASSIGN INPUTS menu information.
6. Operation:
a. e boiler comes on at 0.9VDC and turns o at 0.8VDC. 1VDC = 10%
input. 10VDC = 100% input. ese voltage settings are not adjustable.
b. OUTPUT1 (120VAC) is activated and deactivated as the heat demand is
turned on and o. is output is a good choice to operate the system pump.
7. NOTE: e EVG control can be congured to use either 0–10VDC for target
operation (see previous section) or modulation,
butnotboth.
See Figure65,page59 for details.
N. 120VAC Power Receptacle
Locatedonboilerrightsidepanel
1. Electrical rating is 2.0amps max at 120VAC.
2. is receptacle can be used to plug in a condensate pump.
O. Multiple Boiler and BMS Connections – see ADVANCED Manual
TerminalStripsP4andP5onPump/CommBoard(control tray, left side)
1. e boiler control is capable of multiple boiler communication and control
of up to eight Evergreen
®
boilers in one installation.
2. e boiler control is also capable of BMS communication.
3. e boiler control is also capable ZoneStacking
TM
:
Uses All boiler inputs, not just the rst and last boilers, up to 24 customiz-
able inputs across boiler network (3 per unit, maximum of 8 boilers on the
network).
4. See Evergreen
®
Advanced Manual for multiple boiler installation and setup
information.
See EVG Advanced Manual for details.