Location of Ice Machine
The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met,
select another location.
The location must be free of airborne and other
contaminants.
Self contained air cooled, water cooled or head section
for remote air cooled condenser models - The air
temperature must be at least 35°F (1.6°C), but must
not exceed 110°F (43.4°C).
Remote air cooled condenser - The air temperature
must be at least -20°F (-29°C), but must not exceed
120°F (49°C).
Ice Making Water Inlet - Water Pressure must be
at least 20 psi (1.4 bar), but must not exceed 80 psi
(5.5 bar).
Condenser Water Inlet - Water Pressure must be at
least 20 psi (1.4 bar), but must not exceed 276 psi
(19 bar).
The location must not be near heat-generating
equipment or in direct sunlight and protected from
weather.
The location must not obstruct air flow through or
around the ice machine. Refer to chart below for
clearance requirements.
The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C). Failure
caused by exposure to freezing temperatures is not
covered by the warranty. See “Removal from Service/
Winterization”.
Installation