Loading ...
Loading ...
Loading ...
©2017 Pinnacle Climate Technologies 12 Vent-Free Gas Log Heater User Manual
Installation (cont.)
Minimum Noncombustible Material Clearance—If Not Using a Mantel:
You must have noncombustible material(s) such as slate, tile, or marble above the replace opening. These
materials must be at least 1/2" thick. If using sheet metal, you must have noncombustible material behind it,
such as a noncombustible replace hood accessory (see Fig. 4).
NOTICE: This heater may be used as a vented product. If doing so, you must always operate log set with chimney
ue damper open. If running log set with damper open, noncombustible material above replace opening is
not needed. See INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION, page 14. When used as a
vented decorative appliance, use of the thermostat function is prohibited—operate manually only.
Minimum Noncombustible Material Clearance—If Using a Mantel:
You must have noncombustible material(s) such as slate, tile, or marble at least 1/2" thick. If using sheet
metal, noncombustible material must be behind it. Noncombustible material must extend at least 12" up.
If noncombustible material is less than 12", a replace hood accessory must be installed. If noncombustible
material is more than 12", you may still require the hood accessory to deect heat away from mantel shelf.
See Fig. 3 and 4 above for minimum clearance requirements.
IMPORTANT: If the minimum clearances are not met, you must operate the heater with the chimney ue
damper open. See INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION, page 14.
Heat Resistant
Material
Heat Resistant
Material
(A)
12" min.
Firebox
2 4 6 8 10 12 14 16 18
Inches
Firebox
Inches
Fig. 3—Minimum Clearance for Combustible to Wall
Fig. 4—Heat Resistant Material (slate,
marble, tile, etc.) above Fireplace
Loading ...
Loading ...
Loading ...