Napoleon BGD36CFGN2 Crystallo Series Direct Vent Natural Gas Fireplace

User Manual - Page 31

For BGD36CFGN2.

PDF File Manual, 132 pages, Read Online | Download pdf file

BGD36CFGN2 photo
Loading ...
Loading ...
Loading ...
31
W415-1361 / 11.28.14
EN
* HORIZONTAL VENT SECTIONS - A minimum clearance of 1" (25mm) at the bottom and sides and 2"
(51mm) at the top of the vent pipe on all horizontal runs to combustibles is required. Use restop spacer
W010-1777 (supplied).
* VERTICAL VENT SECTIONS - A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use restop spacer W500-0096 (not supplied).
Minimum clearance to combustible construction from appliance and vent surfaces:
Framing:
- 0" to stand-offs.
Combustible Finishing:
Sides, bottom - 0" to appliance edge.
Top - 6 1/2" (165mm)
Enclosure top - 13 1/2" (343mm) to top of appliance.
Recessed depth - 17 1/4" (438mm)
Top, sides and bottom of vent pipe* - 2" (51mm)
Ceiling - 54" (1372mm) from bottom of appliance.
6.1 INSTALLING STAND-OFFS
These appliances are supplied with two standoffs. For
convenience, the standoffs have been shipped at and located on
the top at the front. Before framing ensure the standoffs are bent
up and screwed into place ensuring a height of 4.5" (144mm).
NOTE: The information and dimensions in this section
represent the minimum clearances to combustible material.
It is best to frame your appliance after it is positioned and the vent
system is installed. Use 2x4's and frame to local building codes.
A steel header is required if using optional clean face surround.