26
Parameters Number
Parameter Name Description
Set options
12
[12] 42V
(Default)
It is recommended to set this
voltage below the maximum
voltage the battery can withstand.
When this voltage is reached, the
loads will be powered off after a
time delay adjustable in Program
13 The range is 38V to 50V, in
0.4V increments
Low Voltage Load
Disconnect
*available in USER
and lithium setting
only
13
[13] 5S
(Default)
The following parameter sets the
delay-time after the battery
voltage is below the set-point in
Program 12. The set range is 5-50
seconds, in 5s increments
Battery
Over-discharged
Delay Time
**If a power
shortage occurs
and recovers in a
short time, it can
cause damage to
your connected
appliances. To
prevent this kind
of damage,
please check
manufacturer if
heavy load
appliances are
equipped with
time-delay function
before installation
*available in USER
and lithium setting
only
*available in USER
and lithium setting
only
14
[14] 43.8V
(Default)
Warning that the battery is
approaching low voltage. The output
does not shut down and the range is
40V to 52V, in 0.4V increments
Battery
Undervoltage
Alarm
*available in USER
and lithium setting
only
15
[15] 40V
(Default)
When the battery voltage goes
below this voltage set-point, the
solar inverter will immediately
disconnect and shut down
immediately. The set range is 36V
to 50V, in 0.4V increments
Battery Discharge
Limit Voltage
*available in FLD
and USER setting
only
*available in FLD
and USER setting
only
16
[16] DIS
[16] ENA
(Default)
Enables equalization charging
No equalization charging
Set Equalization
charging
17
[17] 59.2V
(Default)
Set equalization charging voltage.
The range is 48V to 59.2V, in 0.4V
increments
Battery
Equalization
Voltage