PERFORMANCE DATA | 57
Performance Data
EQUIPMENT SELECTION PROCEDURE
&RUUHFWLRQ)DFWRUV
Cooling / Heating Correction Factors
For Single Zone Mega Wall Mounted systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also,
determine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correc-
tion factors as shown below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity tables using design
conditions. The resultant is the NET cooling or heating capacity.
Cooling and Heating Capacity Coefficient Factors.
Table 31: 0HJD&RROLQJDQG+HDWLQJ&DSDFLW\&RHI¿FLHQW)DFWRUV
Operation
Mode
Piping Length (ft.)
16.4 24.6 32.8 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
Rate of
Capacity
Change (%)
LS-090HEV2
LS-120HEV2
Cooling 100 100 97.7 93.0 -------
Heating 100 100 98.3 95.0 -------
LS-180HEV2
LS-240HEV2
Cooling 100 100 99.0 97.0 95.0 - - - - - -
Heating 100 100 99.2 97.6 96.0 - - - - - -
Equivalent Piping Length for Piping Components
Component Size (Inches)
Elbow (ft.)
1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/8 1-1/4 1-3/8 1-1/2 1-5/8 1-3/4 2-1/8
0.5 0.6 0.7 0.8 1.2 1.3 1.5 1.6 1.8 2.0 2.1 2.3 2.5 2.8
Table 32: 0HJD9&RROLQJDQG+HDWLQJ&DSDFLW\&RHI¿FLHQW)DFWRUV
Altitude Correction Factor
The impact of air density must be considered on systems installed at a significant altitude above sea level, therefore, locally accepted alti-
tude correction factors using ASHRAE guidelines must be applied.
Table 33: Equivalent Piping Length for Elbows.
Operation
Mode
Piping Length (ft.)
16.4 24.6 32.8 49.2 65.6 82.0 98.4 114.8 131.2 147.6 164.0
Rate of
Capacity
Change (%)
LS-090HXV
Cooling 100 100 95.8 87.5 - - - - - - -
Heating 100 100 95.8 93.8 - - - - - - -
LS-180HXV
Cooling 100 100 95.8 87.5 - - - - - - -
Heating 100 100 95.8 93.8 - - - - - - -