12. Restore utility power to the generator.
13. Push the ON/OFF switch to the ON (I) position(see
switch location in the Features and Controls section).
14. Access the generator's controller and set the generator
mode to AUTO.
15. Close and lock the controller access door orclose
and lock the roofas described in the Access Panels:
Installationand Removal section.
NOTICEThis depends on where the generator's controller
is located. See the Access Panels: Installationand Removal
section.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Push the ON/OFF switch to the OFF (0) position(see
switch location in the Features and Controls section).
2. Remove utility power to the generator to de-energize the
battery charger.
3. Unlock and open or removethe roof as described in the
Access Panels: Installationand Removal section.
4. Remove the 15 amp fuse (see fuse location in the
Features and Controls section).
5. Disconnect the negative (-) cable at the battery.
NOTICEFailure to disconnect negative battery cable could
result in equipment failure.DO NOT attempt to jump start
the generator.Damage to equipment resulting from failure to
follow this instruction will void engine and generator warranty.
6. Charge the battery with the battery charger at 2 amps
until the battery holds 12 V. DO NOT exceed 13.7 V
when charging the battery.
NOTICEDO NOT use a battery booster to quick charge a low
battery.
7. Connect the negative (-) cable at the battery.
8. Install the 15 amp fuse into the fuse holder (see fuse
location in the Features and Controls section).
9. Roof and controller:If the generator's controller is
located on one of the side panels of the enclosure –
install the roof if it was removed (see the Access Panels:
Installationand Removal section).If the generator's
controller is located under the roof – do not close or
install the roof yet.
10. Restore utility power to the generator.
11. Push the ON/OFF switch to the ON (I) position(see
switch location in the Features and Controls section).
12. Access the generator's controller and set the generator
mode to AUTO.
13. Close and lock the controller access door orclose
and lock the roofas described in the Access Panels:
Installationand Removal section.
NOTICEThis depends on where the generator's controller
is located. See the Access Panels: Installationand Removal
section.
33