30 31-5000572 Rev. 1
ENGLISH
INSTALLATION INSTRUCTIONS
Electric Wiring and Applications Cont.
Outdoor Machine Digital Tube Display Setting
The contents of the display are defined as follows:
Key parts: long press the left START (SW5) control to enter, short press UP (SW4) data scroll up, short press DOWN
(SW7) data scroll down, long press the right STOP (SW6) enter data and exit.
DIal: SW1, SW2, SW3: set the rotary dial switch is 0-15.
NOTE: The dial plate, with the letters A for 10, B for 11, C for 12, D for 13, E for 14, F for 15.
Display parts: LD1, LD2, LD3, LD4:4 digital tube from left to right.
1. Indoor Machine Parameter View
You can view the indoor machine 128 sets of parameters: SW1 and SW2 represent the indoor machine address, SW3
range 3-14 can view the indoor machine parameters.
SW1 SW2 Address
0 0-15 1 to 16 (address 0# - 15#)
1 17 to 32 (address 16# - 31#)
2 33 to 48 (address 32# - 47#)
3 49 to 64 (address 48# - 63#)
7 65 to 80 (address 64# - 79#)
8 81 to 96 (address 80# - 95#)
9 97 to 112 (address 96# - 111#)
10 113 to 128 (address 112# - 127#)
SW3 Function Digital Tube LD1 ~ 4 Display
3 Indoor unit communication check and
program version
Communication normal display indoor machine program version (1 decimal), the
communication interrupted normal display “0000 (5 consecutive rounds ofno
Communication” success,), communication has not been normal display---- ----””. Such as
3.9, said the machine version number is V3.9
4 Indoor unit failure Display indoor unit fault code, no fault display 0
5 Indoor unit capacity The indoor unit capacity (tonnage, 1 decimal places), 1.5 tonnage show 1.5
6 Indoor unit expansion valve opening expansion valve opening (pulse)
7 Indoor unit environment temperature
Tai
zone temperature (°F )
8 Indoor gas temperature Tc1 gas temperature Tc1 (°F)
9 Indoor liquid temperature Tc2 liquid temperature (°F)
10 (A) Indoor unit boot mode, the actual
operation of wind speed and SCODE
code
LD1 said the boot mode O: stop C: refrigeration H: heating
LD2 said the actual operating speed of the indoor machine (0- stop, 1- low
speed, 2- Middle speed , 3- high speed),
LD3 and LD4 are represented by SCODE codes (0 ~ 15)°
Such as C311 said the cooling operation of high speed, SCODE 1
11 (B) Indoor set temperature Tset Indoor set point temperature (°F)
12 (C) Indoor unit consistancy control
setting
Display the indoor unit corresponding to the same contract use (0 unallocated group number,
their control) Method of setting group and the <E2 control parameters and Display Settings
> (Note: all in the unit at the same time can be set by a dial 15-0-2 set “in the same unit drive
outside unit control, 0- indoor unit according to the number of automatic control, 1- indoor
unit with all contract, all within each 2- indoor unit control, banned from drive off)
SW3 Function Digital Tube LD1 ~ 4 Display
13 (D) Low temperature automatic
running function of indoor unit
Òñçìæä÷èöìéðäæëìñèëäö÷ëìöéøñæ÷ìòñòõñò÷ ñò!üèö
Use E2 control parameters display and settings.
Access by setting dial switches to 15-1-2. Set low temperature and automatic operation at the same
time.
0=automatic control
1= all machine settings valid
2= all machine settings not valid
14 (E) Forced indoor unit cooling /
heating / shutdown
¤!¥ÙõèööÜÝÊÛÝ¤Üà%¥éòõ"ö÷òèñ÷èõ÷ëèìñö÷õøæ÷ìòñöè÷ö÷ä÷èĩäöëìñêçìöóïäüìñö÷õøæ÷ìòñö
(2) according to UP (SW4) or DOWN (SW7) () adjustment instructions (COOL/HEAT/OFF).
(3) after the adjustment is completed, according to STOP (SW6) for 2 s,the implementation of the
ìñö÷õøæ÷ìòñöè÷äñçö÷òóĩäöëìñêçìöóïäü