31-5000572 Rev. 1 23
ENGLISH
INSTALLATION INSTRUCTIONS
Additional Refrigerant Charging
• Charge the additional refrigerant as liquid using a digital refrigerant scale and manifold gauges.
Charge the system in trail mode. Compressor failure can occur if the system runs for a prolonged period of time while
undercharged.
• Charging must be complete within a 30 minute period.
The unit is only partially charged from the factory and will need additional refrigerant. Refer to the report generated by
the system design software.
– W1: Refrigerant charging volume to outdoor unit at factory.
– W2: Refrigerant charging volume to liquid pipe base on different piping length calculation.
W2=actual length of liquid pipe×additional amount per ft liquid pipe=
(L1×3.76)+(L2×2.69)+(L3×1.83)+(L4×1.18)+(L5×0.58)+(L6×0.24)
¢Õ!Ýò÷äïïèñê÷ëòé'¦(¤""""¥ïìôøìçóìóè
¢Õ"Ýò÷äïïèñê÷ëòé#¦$¤!) %¥ïìôøìçóìóè
¢Õ#Ýò÷äïïèñê÷ëòé%¦(¤!%((¥ïìôøìçóìóè
¢Õ$Ýò÷äïïèñê÷ëòé!¦"¤!"'¥ïìôøìçóìóè
¢Õ%Ýò÷äïïèñê÷ëòé#¦(¤)%"¥ïìôøìçóìóè
– L6:Total length of 1/4(6.35) liquid pipe
• Total refrigerant volume charging on site during installation=W2
– W: Total refrigerant volume charging on site for maintenance.
Note:
Do not use manifold gages and hoses that were used on equipment with oil other than PVE.
Cross contamination can occur.
• Refrigerant R410A is identified by a pink tank color or label.
• Charging cylinders cannot be used as R410A refrigerant will fractionate.
Always charge R410A refrigerant using liquid. Write the final charge weight on the unit near the name plate
for future reference.
Ýëèóõòçøæ÷æòñ÷äìñöĩøòõìñä÷èçêõèèñëòøöèêäöèöäñçì÷öéøñæ÷ìòñìñêõèïìèöøóòñöøæëêäöèö
REFRIGERANT RECORD FORM
Model
W1:
Refrigerant
charging volume
to outdoor unit
at factory
W2:
Refrigerant charging volume to liquid pipe base on different piping
length calculation
Total refrigerant
Volume charging
on site during
installation
W: Total refrigerant volume
charging on Liquid pipe site
for maintenance
Liquid pipe
Diameter in(mm)
Additional refrigerant amount Oz/ft
072 511.5 oz 1/4(6.35) 0.24 Oz/ft×__ft=__ Oz
W2=___ Oz W1+W2=___ Oz
096 754.8 oz 3/8(9.52) 0.58 Oz /ft×__ft=__ Oz
120 754.8 oz 1/2(12.7) 1.18 Oz /ft×__ft=__ Oz
144 698.4 oz 5/8(15.88) 1.83 Oz /ft×__ft=__ Oz
3/4(19.05) 2.69 Oz /ft×__ft=__ Oz
7/8(22.22) 3.76 Oz /ft×__ft=__ Oz