SiUS121827E Common Functions
Part 4 Functions and Control 59
1. Common Functions
1.1 Temperature Control
Definitions of
Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
The illustration is for wall mounted type as representative.
Temperature
Control
The temperature of the room is detected by the room temperature thermistor. However, there is a
difference between the temperature detected by room temperature thermistor and the temperature
of lower part of the room, depending on the type of the indoor unit or installation condition. In
practice, the temperature control is done by the target temperature appropriately adjusted for the
indoor unit and the temperature detected by room temperature thermistor.
1.2 Frequency Principle
Control
Parameters
The frequency of the compressor is controlled by the following 2 parameters:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to control
the rotation speed of the compressor. The followings explain the inverter principle:
Phase 1
The supplied AC power source is converted into the DC power source for the present.
Phase 2
The DC power source is reconverted into the three phase AC power source with variable
frequency.
Target temperature
Set temperature
Room temperature
Room thermistor temperature
(R12321)