1311298 Daikin Dual-Zone Mini Split System with with 47000 BTU Cooling Capacity, 48500 BTU Heating Capacity and 2x Wall Mounted Indoor Units

User Manual - Page 127

For 1311298.

PDF File Manual, 299 pages, Read Online | Download pdf file

1311298 photo
Loading ...
Loading ...
Loading ...
SiUS121827E Control Specification
Part 4 Functions and Control 121
Reference
4.14 Malfunctions
4.14.1 Sensor Malfunction Detection
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Gas pipe thermistor
5. Outdoor temperature thermistor
6. Liquid pipe thermistor
4.14.2 Detection of Overcurrent and Overload
Outline In order to protect the inverter, an excessive output current is detected and the OL temperature is
observed to protect the compressor.
Details If the inverter current exceeds 27.5 ~ 29 A (depending on the model), the system shuts down
the compressor.
If the OL (on the side of the compressor body) temperature exceeds 125°C (257°F), the
compressor stops.
4.14.3 Refrigerant Shortage Control
Outline If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as refrigerant shortage.
The power consumption is low comparing with that in the normal operation when refrigerant is
insufficient, and refrigerant shortage is detected by checking power consumption.
R4003425
Refer to Refrigerant shortage on page 195 for details.
4.14.4 Anti-icing Function
During cooling, if the indoor heat exchanger temperature in the room not in operation becomes
below the specified temperature for the specified time, the electronic expansion valve is opened in
the operation stopped room as specified, and the fully closed operation is carried out. After this, if
freezing abnormality occurs longer than specified time, the system shuts down as the system
abnormality.
Frequency
Refrigerant shortage zone
40 Hz
Power consumption
(Input current)
Loading ...
Loading ...
Loading ...