Troubleshooting for Outdoor Unit SiUS121827E
208 Part 6 Service Diagnosis
7.8 Compressor Lock
Error Code E6
Outdoor Unit LED
Display
A j 1 h 2 i 3 i 4 h 5 h
Method of Error
Detection
A compressor lock is detected by checking the compressor running condition through the position
detection circuit.
Error Decision
Conditions
Judging from the current waveform generated when high-frequency voltage is applied to the
compressor.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Closed stop valve
Defective outdoor unit PCB
Defective compressor
Defective electronic expansion valve