SiUS121827E Field Settings
Part 7 Trial Operation and Field Settings 265
Note(s)
5.2.2 Overview of Field Settings for FFQ Series
Factory Setting
Any function that is not available on the indoor unit us not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01 02 03 04 05 06
10
(20)
0
Filter cleaning
sign interval
Longlife filter
Light
Approx.
2,500 hrs.
Heavy
Approx.
1,250 hrs.
————
2 Remote controller thermistor Enabled Disabled ————
3 Filter cleaning sign Display No display — — — —
12
(22)
0
Optional accessories output
selection (field selection of
output for adaptor for wiring)
Compressor —
Operation
output
Error
output
Outdoor
air
intake
Presence
sensor
13
(23)
0
High air outlet velocity (for
high ceiling applications)
≤ 2.7 m
(≤ 8-7/8 ft)
2.7 ~ 3.0 m
(8-7/8~9-13/16 ft)
3.0 ~ 3.5 m
(9-13/16~11-1/2 ft)
———
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow 3-way flow 2-way flow — — —
4 Airflow direction range setting Upper Normal Lower — — —
15
(25)
3
Drain pump operation with
humidifying
Not equipped Equipped — — — —