Field Settings SiUS121827E
266 Part 7 Trial Operation and Field Settings
Note(s)
5.2.3 Overview of Field Settings for FDMQ Series
Factory Setting
The Second Code No. is factory set to "01".
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the
group are equal.
For group control, refer to the installation manual attached to the indoor unit for group control.
External Static Pressure Settings
Factory Setting
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01 02 03 04 05 06
10
(20)
0
Filter cleaning
sign interval
(used to change
filter cleaning
display interval
according to filter
contamination)
Longlife
filter
Light
Approx.
2,500
hrs.
Heavy
Approx.
1,250
hrs.
————
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
————
3
Filter cleaning sign (used to
set filter cleaning display ON/
OFF)
Display No display————
11
(21)
7
Air volume adjustment
OFF
Air volume
adjustment
completion
Air volume
adjustment
start
———
13
(23)
6
External static pressure Refer to the table below.
Mode
No.
First
Code
No.
Second Code No.
External static pressure
09/12
Class
15/18/24
Class
13
(23)
6
03
30 Pa (0.12 inH
2
O)
04
40 Pa (0.16 inH
2
O)
05 05 50 Pa (0.20 inH
2
O)
06 06 60 Pa (0.24 inH
2
O)
07 07 70 Pa (0.28 inH
2
O)
08 08 80 Pa (0.32 inH
2
O)
09 09 90 Pa (0.36 inH
2
O)
10 10 100 Pa (0.40 inH
2
O)
11 11 110 Pa (0.44 inH
2
O)
12 12 120 Pa (0.48 inH
2
O)
13 13 130 Pa (0.52 inH
2
O)
14 14 140 Pa (0.56 inH
2
O)
15 15 150 Pa (0.60 inH
2
O)