SiUS121827E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 225
Notes
Reference
Troubleshooting In case of H9, J3, J6, J8, J9
H9 : Outdoor temperature thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor heat exchanger thermistor
J8 : Liquid pipe thermistor
J9 : Gas pipe thermistor
When replacing the defective thermistor(s), replace the thermistors as ASSY.
Check No.01 Refer to P.232
(R21118)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3 error: The discharge
pipe temperature is lower
than the heat exchanger
temperature.
Replace the defective
thermistor(s).
Outdoor temperature
thermistor
Discharge pipe thermistor
Outdoor heat exchanger
thermistor
Liquid pipe thermistor
Gas pipe thermistor
Cooling: Outdoor heat
exchanger
thermistor
Heating: Indoor heat
exchanger
thermistor
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Error displayed
again on remote controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.