J.RoutineMaintenance
NOTE: Units are to be inspected and serviced by qualified service personnel only.
1. Cleantheunitair intakefilter atleast every 300 to350 hours
of operation. Cleanthefilters with a milddetergent inwarm
water and allow to dry thoroughly before reinstalling.
2. The indoorcoil(evaporatorcoil),theoutdoorcoil(condenser
coil) and base pan should be inspected periodically (yearly
or bi-yearly)andcleaned ofalldebris(lint,dirt, leaves,paper,
etc.). Clean the coils and base pan with a soft brush and
compressed airor vacuum. Ifusing a pressure washer, be
careful notto bend thealuminium fin pack. Use asweeping
upand down motionin thedirectionofthevertical aluminum
fin pack when pressure cleaning coils. Cover all electrical
components to protect them fromwater orspray.
Before reinstalling the chassis in the sleeve, inspect the
indoor blowerhousing, blowerwheel, condenser fan blade,
and condenser shroud periodically (yearly or bi-yearly) and
clean of all debris (lint, dirt, mold, fungus, etc.) Clean the
blowerhousingarea and blowerwheel with an antibacterial
/ antifungal cleaner. Use a biodegradable cleaning agent
and degreaser on condenser fan and condenser shroud.
Use warm or cold water when rinsing these items. Allow
the unit to dry thoroughly, inspect all gasket material for
deterioration (replace as necessary), and then reinstall the
chassis in the sleeve.
,
,
Periodically (at least yearly or bi-yearly): inspect all control
components, both electricaland mechanical, aswell asthe
power supply. Use proper testing instruments (voltmeter,
ohmmeter, ammeter, wattmeter, etc.) to perform electrical
tests. Use an air conditioning or refrigeration thermometer
to check room, outdoor and coil operating temperatures.
Useaslingpsychrometertomeasurewet bulbtemperatures
indoors and outdoors.
Inspectthe surroundingarea (insideand outside)to ensure
that the units' clearances have not been compromised or
altered.
Inspect the sleeve and drain system periodically (at least
yearly or bi-yearly) and clean ofall obstructions and debris.
Clean both areas with an antibacterial and antifungal
cleaner. Rinse bothitemsthoroughlywithwater andensure
that the drain outlets are operating correctly. Check the
sealant around the sleeve and reseal areas as needed.
Clean the front cover when needed. Use a mild detergent.
Wash and rinse with warm water. Allow them to dry
thoroughly before reinstalling them in the chassis.
NOTE: Do not use a caustic coil cleaning agent on coils
or base pan. Use a biodegradable cleaning agent and
degreaser.