The fixed consumer piping outlet should be at
approximately the same height as the cooker
connection point, pointing downwards and
approximately 150mm to the side of the cooker. The
hose should be clear of the floor when the cooker is
in the installed position. Ensure that the safety chain
is installed correctly so that the chain prevents strain
on the hose connections when the cooker is pulled
forward.
If the connection is for natural gas the test point
pressure should be adjusted to 1.00kPa with the wok
burner operating at maximum.
GAS CONNECTION
If installing for use with LPG ensure that an AGA
approved gas regulator suitable for a supply pressure
of 2.75kPa is part of the tank supply and the test point
pressure is adjusted to 2.75kPa.
- There is a connection kit supplied with the cooker.
The extension tube must be attached to the inlet
elbow on the cooker. At the other end of the tube
attach the regulator (for Natural Gas) using the
brass conical adaptor with the sealing washer.
Use two spanners to tighten to prevent strain
on the inlet tube.
- It is recommended that an isolating valve and union
be fitted, to enable simple disconnection for servicing.
These are to be in an accessible location.
- Check connections are gas tight with soapy water or
other approved method.
- Under no circumstances use a naked flame in
checking for leaks.
- Check Gas Adjustments (refer installation - gas
checks and adjustments).
- When satisfied that the upright cooker is operating
correctly, instruct the customer in its safe operation.
Ensure the customer understands fully by having
them operate the upright cooker in all its functions.
N
A
T
G
A
S
L
P
G
G
A
S
Natural Gas
LPG Gas
OR
Gas Flow
Gas Flow Gas Flow