W415-1407 / 11.20.14
27
EN
1"
25mm
MIN
44"
1118mm
29"
737mm
62 1/8"
1578mm
1"
25mm
MIN
22 1/2"
572mm
29"
737mm
10"
254mm
MIN
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES
!
WARNING
MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED OR A SERIOUS FIRE HAZARD
COULD RESULT.
WHEN CONSTRUCTING THE ENCLOSURE ALLOW FOR FINISHING MATERIAL THICKNESS TO
MAINTAIN CLEARANCES. FRAMING OR FINISHING MATERIAL CLOSER THAN THE MINIMUMS
LISTED MUST BE CONSTRUCTED ENTIRELY OF NON-COMBUSTIBLE MATERIALS. MATERIALS
CONSISTING ENTIRELY OF STEEL, IRON, BRICK, TILE, CONCRETE, SLATE, GLASS OR PLASTERS,
OR ANY COMBINATION THEREOF ARE SUITABLE. MATERIALS THAT ARE REPORTED AS PASSING
ASTM E 136, STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE
FURNACE AT 750°C AND UL763 SHALL BE CONSIDERED NON-COMBUSTIBLE MATERIALS.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
Maintain these minimum clearances to combustibles from appliance and vent surfaces
Non-combustible appliance nishing:
- 4" (102mm) from the sides of the appliance opening
- 22 3/8" (568mm) to the top of the appliance opening
Combustible appliance nishing:
- 0" (0mm) to rear
- 2" (51mm) all around the vent pipe*
- 22 1/2" (572mm) recessed depth
- 64" (1626mm) from the bottom of the appliance to the ceiling
- 72" (1829mm) from bottom of appliance to the enclosure top
*HORIZONTAL VENT SECTIONS: A minimum clearance of 2" (51mm) all around the vent pipe on all horizontal runs
to combustibles is required. Use restop spacer W010-1799 (supplied).
*VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles
is required except for clearances in appliance enclosures. Use restop spacer W500-0096 (not supplied).