W415-1407 / 11.20.14
10
EN
!
WARNING
THE FIRST 2 FEET OF OUTER 7" (178MM) DIAMETER VENT PIPE FROM THE APPLIANCE MUST
BE WRAPPED IN THE 1" (25MM) THICK INSULATION SLEEVE (SUPPLIED). MAKE SURE THE
INSULATION IS PULLED DOWN TIGHT TO THE APPLIANCE WHEN INSTALLED. THERE AFTER, A
2" (51MM) CLEARANCE ALL AROUND THE VENT PIPE FROM COMBUSTIBLE MATERIALS ON ALL
HORIZONTAL VENT SECTIONS IS REQUIRED.
45.6
10" (254mm)
MINIMUM
24" (610mm)
MAXIMUM
56"
(1422mm)
PLUS RISE
46"
(1168mm)
16" (406mm)
MINIMUM
3 FEET (1m)
MINIMUM
40 FEET (12m)
MAXIMUM
When venting, the horizontal run must be kept to a maximum of 20 feet (6m). If a 20 foot (6m) horizontal run
is required, the appliance must have a minimum vertical rise immediately off the appliance of 57" (1448mm).
When terminating vertically, the vertical rise is a minimum 3 feet (1m) and a maximum 40 feet (12m) above the
appliance.
* FIRST TWO
FEET
REQUIRES
INSULATION
SLEEVE
3.2 TYPICAL VENT INSTALLATION
46"
(1168mm)
* First two feet (0.6m) requires insulation sleeve