BLDV7 Series Gas Fireplace
VENTING INSTALLATION
Step 7
Guide the vent terminations 4” and 7” collard into their
respective vent pipes. Double check that the vent pipes
overlap the collars by 2” (51 mm). Secure the termination
to the wall with screws provided and caulk around the
wall plate to weatherproof. As an alternative to screwing
the termination directly to the wall, you may also use ex-
panding plugs or an approved exterior construction ad-
hesive. You may also attach the termination with screws
through the inner body into the 4” vent pipe, however
for this method, you must extend the 4” pipe approxi-
mately 6” (152 mm) beyond the outer face of the wall.
Support horizontal pipes every 36” (914
mm) with metal pipe straps.
VERTICAL SIDEWALL INSTALLATION -
FLEX VENT PIPE
NOTE:The40”(1016mm)exventisusedfor90°bend
after a straight vertical section (12" min.) then out the
back wall. Figure 20
Follow Steps 1 - 3 on Page 17.
Step 4
Installthefour(4)spacerspringsonthe4”exventpipe.
When installing the spacer springs around the 4” pipe,
stretch the spring to approximately 15” (381 mm), wrap
the spring around the pipe and interlock the ends of the
spacer spring approximately 2” (51 mm). Measure 183/4”
(476 mm) from the end of the pipe. Place the next spring
5” (127 mm) from the previously installed spring. Place
the next spring 6” (152 mm) from the last spring. Finally
place the last spring 12” (305 mm) from the last spring
installed. Figure 19
Step 5
Installthe4”(102mm)exventpipetotheappliancecol-
larasdescribedonPage13.Securetheendwiththerst
spring183/4”(476mm)fromtheexpipeendtotheunit.
Step 6
Slidethe7”(178mm)exventpipeoverthe4”exvent
pipe and secure the 7” collar as described on Page 13.
Step 7
Bendtheexpipehorizontalsothebottomofthehorizon-
tal pipe measure 181/2” (470 mm) from the top of the unit
immediately after the 90° formation. Figure 20. Be sure to
followthe1/2”(13mm)riseina12”(305mm)horizontal
run rule.
Step 8
Installthe4”exthen7”extothetermination.
12"
(305 mm)
6"
(152 mm)
5"
(127 mm)
18³⁄₄"
(476 mm)
FP1474
spacer springs
4/04 djt
4" Flex
Vent Pipe
Spacer
Spring
FP1474
Figure 19 -
Install Spacer Springs
*18¹⁄₂"
(470 mm)
Min.
FP1475
flex 90 bend
4/04 djt
Figure 20 -
Bend Flex Vent at
90° so Horizontal
Portion is 181/2"
(470 mm) Off Top of
Unit
FP1475
BELOW GRADE INSTALLATION
When it is not possible to meet the required vent terminal
clearances of 12” (305 mm) above grade level, a snor-
kel kit is recommended. It allows installation depth down
to 7” (178 mm) below grade level. The 7” (178 mm) is
measuredfromthecenterofthehorizontalventpipeasit
penetrates through the wall.
Ensure the sidewall venting clearances are observed.
If venting system is installed below ground, we rec-
ommend a window well with adequate and proper
drainage to be installed around the termination area.
If installing a snorkel, a minimum 24” (610 mm) vertical
riseis necessary.The maximumhorizontal run with the
24” vertical pipe is 36” (914 mm). This measurement is
takenfromthecollarofthereplace(ortransitionelbow)
to the face of the exterior wall. See the Sidewall Venting
Graphforextendedhorizontalruniftheverticalexceeds
24” (610 mm).
1. Establish vent hole through the wall. Page 17, Figure 16
*Includes collar height,
12" straight section and
bend radius.