Trial Operation and Testing
(QTYKTGNGUUTGOQVGEQPVTQNNGT
1) Press
MODE
CPFUGNGEVVJG%11.QT*'#6QRGTCVKQP
2) Press
/TEST
twice. “Test” is displayed.
3) Press
ON OFF
within 10 seconds, and the test operation starts.
Monitor the operation of the indoor unit for a minimum of 10 minutes. During test operation, the indoor unit will continue to
cool/heat regardless of the temperature setpoint and room temperature.
r In the case of above-mentioned procedures 1) and 2) in reverse order, test operation can start as well.
r Test operation will stop automatically after 15 - 30 minutes. To stop the operation, press
ON OFF
.
r Some of the functions cannot be used in the test operation mode.
Precautions
1) Refer to p*QYVQFKCIPQUGHQTOCNHWPEVKQPq if the unit does not operate properly.
2. 6GUVKVGOU
Test items Symptom Check
Indoor and outdoor units are installed securely. Fall, vibration, noise
Is the outdoor unit fully installed? No operation or burn damage
No refrigerant gas leaks. Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose
extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
Does the power supply voltage correspond to that
shown on the name plate?
No operation or burn damage
1PN[URGEKƂGFYKTGUCTGWUGFHQTCNNYKTKPICPFCNN
wires are connected correctly.
No operation or burn damage
System is properly grounded. 'NGEVTKECNNGCMCIG
+UYKTKPIUK\GCEEQTFKPIVQURGEKƂECVKQPU! No operation or burn damage
Is something blocking the air outlet or inlet of either the
indoor or outdoor units?
Incomplete cooling/heating function
Are refrigerant piping length and additional refrigerant
charge noted down?
The refrigerant charge in the system is not clear
Pipes and wires are connected to the corresponding
connection ports / terminal blocks for the connected unit.
No cooling/heating
Stop valves are opened. Incomplete cooling/heating function
Check that the connector of the lead wires of the
decoration panel is connected securely.
Louvers do not move
Indoor unit properly receives wireless remote control
commands.
No operation
+VGOUVQDGEJGEMGFCVVKOGQHFGNKXGT[
Also review the p2TGECWVKQPUq on page 3
Test items Check
#TGVJGGNGEVTKECNYKTKPIDQZEQXGTCKTƂNVGTUWEVKQPITKNNGCVVCEJGF!
Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual over to your customer?
2QKPVUHQTGZRNCPCVKQPCDQWVQRGTCVKQPU