Selectingpipesize(Fig.4-3)
A B
Liquid (mm) ø9.52
The piping connection size differs according to the type
and capacity of indoor units. Match the piping connec-
tion size of branch box with indoor unit.
If the piping connection size of branch box does not
match the piping connection size of indoor unit, use
optional different-diameter (deformed) joints to the
branch box side. (Connect deformed joint directly to
the branch box side.)
Gas (mm) ø15.88
L: The farthest piping length for the main pipes from the outdoor unit to the branch
box.
Different-diameterjoint(optionalparts)(Fig.4-4)
Model name
Connected pipes diameter Diameter A Diameter B
mm mm mm
MAC-A454JP ø9.52→ø12.7 ø9.52 ø12.7
MAC-A455JP ø12.7→ø9.52 ø12.7 ø9.52
MAC-A456JP ø12.7→ø15.88 ø12.7 ø15.88
PAC-493PI ø6.35→ø9.52 ø6.35 ø9.52
PAC-SG76RJ-E ø9.52→ø15.88 ø9.52 ø15.88
Different-diameterjoint(optionalparts)(Fig.4-5)
Model name
Connected pipes diameter
Outside
Diameter A
Inside
Diameter B
mm mm mm
PAC-SG78RJB-E
ø9.52→ø12.7
ø9.52 ø12.7
PAC-SG79RJB-E
ø12.7→ø9.52
ø12.7 ø9.52
PAC-SG80RJB-E
ø12.7→ø15.88
ø12.7 ø15.88
PAC-SG77RJB-E
ø6.35→ø9.52
ø6.35 ø9.52
PAC-SG76RJB-E
ø9.52→ø15.88
ø9.52 ø15.88
2-branchespipe(Joint):Optionalparts(Accordingtotheconnectionmethod,
youcanchoosethefavoriteone.)
Model name Connection method
MSDD-50AR-E are
■Installationprocedure(2branchespipe(Joint))
Refer to the installation manuals of MSDD-50AR-E.
■
Pipesize(Outdoorunit-Branchbox)
Pipe size
(ømm)
Liquid ø9.52
Gas ø15.88
The lineup of aconnectable indoor unit depends on a district/areas/
country.
■
Branchbox
Model name Numberofconnectedunits
PAC-MK3
✽
BC 3-branches (Max. 3 units)
PAC-MK5
✽
BC 5-branches (Max. 5 units)
Note:
✽
=0,1,2,....
ThePAC-MK31/32BCandPAC-MK51/52BCcannotbeconnected.
■
Pipesize(Branchbox–Indoorunit)CaseofMseriesorSseriesindoorunit
Indoor
unit type
(kW) 22 – 42 50 60 71 – 80
Pipe size
(ømm)
Liquid ø6.35 ø6.35 ø9.52
Gas ø9.52 ø12.7 ø15.88 ø15.88
* If the pipe size of indoor unit is different, use a different-diameter joint.
■
Pipesize(Branchbox–Indoorunit)CaseofPseriesindoorunit
Indoor
(kW) 35 – 50 60 – 100
unit type
Pipe size
(ømm)
Liquid ø6.35 ø9.52
Gas ø12.7 ø15.88
*1 The lineup of aconnectable indoor unit depends on a district/areas/
country.
*2 Whenusing35,50typeindoorunitofPseries,usethearenutattached
totheindoorunit.
Donotusethearenutintheindoorunitaccessory.Ifitisused,agas
leakageorevenapipeextractionmayoccur.
(1) Valve size for outdoor unit
For liquid ø9.52mm
For gas ø15.88mm
(2) Valve size for branch box
AUNIT
Liquid pipe ø6.35mm
Gas pipe ø9.52mm
BUNIT
Liquid pipe ø6.35mm
Gas pipe ø9.52mm
CUNIT
Liquid pipe ø6.35mm
Gas pipe ø9.52mm
DUNIT
Liquid pipe ø6.35mm
Gas pipe ø9.52mm
EUNIT
Liquid pipe ø6.35mm
Gas pipe ø12.7mm
* 3-branch type : only A, B, C unit
B
A
Fig.4-4
Fig.4-3
A
B B B B B
L
Branch box (PAC-MK∙BC)
■Incaseofusing1-branchbox
Flareconnectionemployed.(No.brazing)
■Incaseofusing2-branchboxes
Branchbox#1(PAC-MK∙BC)
2 branches pipe (joint) (MSDD)
: optional parts.
Branchbox#2(PAC-MK∙BC)
Conversion formula
1/4F ø6.35
3/8F ø9.52
1/2F ø12.7
5/8F ø15.88
3/4F ø19.05
4. Installingtherefrigerantpiping
Fig.4-5
A (outside) B (inside)
RG79Y960H01.indb 9 2018/02/09 14:31:05