6. Electricalwork
ThicknessofWireforMainPowerSupplyandOn/OffCapacities
Model
Power supply
Minimum Wire Thickness (mm²)
Breaker for
Wiring *1
Breaker for Current Leakage
Main Cable Ground
Outdoor unit
~/N220-230-240V50Hz
~/N220V60Hz
When power is supplied
separately
6.0 6.0
32 A 32 A 30 mA 0.1 sec. or less
When power is supplied from
the outdoor unit
6.0 6.0
40 A 40 A 30 mA 0.1 sec. or less
3N~380-400-415V50Hz
3N~380V60Hz
When power is supplied
separately
2.5 2.5
16 A 16 A 30 mA 0.1 sec. or less
When power is supplied from
the outdoor unit
4.0 4.0
25 A 25 A 30 mA 0.1 sec. or less
Indoorunit/
Branch box
~/N220-230-240V50Hz
~/N220V60Hz
Refer to the following indoor unit or branch box wiring and breaker capacity calculation.
*1.Abreakerwithatleast3.0mmcontactseparationineachpolesshallbeprovided.Useearthleakagebreaker(NV).
Total operating current of the indoor unit
Minimum wire thickness (mm²)
Ground-fault interrupter *1
Local switch (A)
Breaker for wiring
(NFB)
Main Cable Branch Ground
Capacity Fuse
F0 = 16 A or less *2
1.5 1.5 1.5
20 A current sensitivity *3 16 16 20
F0 = 25 A or less *2
2.5 2.5 2.5
30 A current sensitivity *3 25 25 30
F0 = 32 A or less *2
4.0 4.0 4.0
40 A current sensitivity *3 32 32 40
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2={V1×(QuantityofType1)/C}+{V1×(QuantityofType2)/C}+···+{V1×(QuantityofType16)/C}
Connect to Branch box (PAC-MK·BC)
Indoor unit V1 V2
Type 1 PEAD-RP·JAA 26.9
2.4
Type 2 SEZ-KD·VA(L), PLA-RP·BA, PCA-RP·KAQ 19.8
Type 3 SLZ-KF·VA3 17.1
Type 4 MLZ-KP·VF-A 9.9
Type 5 MFZ-KJ·VE-A1,MSZ-AP·VGD-A1 7.4
Type 6 MSZ-GE·VAD-A1, MSZ-FH·VE-A1, MSZ-EF·VE2-A1 6.8
Type 7 SLZ-KA·VA(L) 3.5
Type 8 Branch box (PAC-MK·BC) 5.1 3.0
Connect to Connection kit (PAC-LV11M)
Indoor unit V1 V2
Type 9 MSZ-AP·VGD 7.4
2.4Type 10 MSZ-GE·VAD, MSZ-EF·VE2, MSZ-FH·VE 6.8
Type 11 Connection kit (PAC-LV11M) 3.5
Indoor unit V1 V2
Type 12 PEFY-P·VMA(L)-E, PEFY-P·VMA3-E 38.0 1.6
Type 13
PMFY-P·VBM-E, PLFY-P·VBM-E, PLFY-P·VFM-E1, PEFY-P·VMS1(L)-E,
PCFY-P·VKM-E, PKFY-P·VHM-E, PKFY-P·VKM-E, PFFY-P·VKM-E2,
PFFY-P·VLRM(M)-E
19.8
2.4
Type 14 PLFY-P·VCM-E2 9.9
Type 15 PKFY-P·VBM-E 3.5
Type 16
PLFY-P·VLMD-E,PEFY-P·VMH(S)-E,PEFY-P·VMR-E-L/R,
PEFY-P·VMH-E-F, PFFY-P·VLEM-E
0 0
C : Multiple of tripping current at tripping time 0.01s
Please pick up “C” from the tripping characteristic of the breaker.