6 Value Series Manual
Environment
Air surrounding the water heater, venng, and vent
terminaon(s) is used for combuson and must be free
of any compounds that cause corrosion of internal
components. These include corrosive compounds that
are found in aerosol sprays, detergents, bleaches,
cleaning solvents, oil based paints/ varnishes, and
refrigerants. The air in beauty shops, dry cleaning
stores, photo processing labs, and storage areas for pool
supplies oen contains these compounds. Therefore it
is recommended that outdoor models be used for these
locaons where possible.
The water heater, venng, and vent terminaon(s)
should not be installed in any areas where the air may
contain these corrosive compounds. If it is necessary for
a water heater to be located in areas which may contain
corrosive compounds, the following instrucons are
strongly recommended.
IMPORTANT CONSIDERATIONS FOR:
Indoor/Internal Water Heaters
DO NOT Install in areas where air for combuson
can be contaminated with chemicals.
Before installaon, consider where air has the
ability to travel within the building to the water
heater.
Where possible, install the water heater in a sealed
closet so that it is protected from the potenal of
contaminated indoor air.
Chemicals that are corrosive in nature should not
be stored or used near the water heater.
Outdoor/External Water Heaters and Vent
Terminaons of Indoor/Internal Water Heaters
Install the water heater as far away as possible
from exhaust vent hoods.
Install as far away as possible from air inlet vents.
Corrosive fumes may be released through these
vents when air is not being brought in through
them.
Chemicals that are corrosive in nature should not
be stored or used near the water heater or vent
terminaon.
Damage and repair due to corrosive compounds in the
air is not covered by warranty.
Consideraon of care for your water heater should
include evaluaon of water quality.
The water must be potable, free of corrosive chemicals,
sand, dirt, or other contaminates. It is up to the
installer to ensure the water does not contain corrosive
chemicals, or elements that can aect or damage the
heat exchanger. Water that contains chemicals
exceeding the levels below aect and damage the heat
exchanger. Replacement of the heat exchanger due to
water quality damage is not covered by the warranty.
Maximum Level
Total Hardness Up to 200 mg / L
Aluminum * Up to 0.2 mg / L
Chlorides * Up to 250 mg / L
Copper * Up to 1.0 mg / L
Dissolved Carbon Dioxide (CO2) Up to 15.0 mg / L or PPM
Iron * Up to 0.3 mg / L
Manganese * Up to 0.05 mg / L
pH * 6.5 to 8.5
TDS (Total Dissolved Solids) * Up to 500 mg / L
Zinc * Up to 5 mg / L
Determine Installaon Locaon
Water Quality
* Source: Part 143 Naonal Secondary Drinking Water
Regulaons
If you install this water heater in an area that is known
to have hard water or that causes scale build-up the
water must be treated and/or the heat exchanger
ushed regularly.
When scale build-up in the heat exchanger begins to
aect the performance of the water heater, a diagnosc
code “LC#” will display. Flush the heat exchanger to
prevent damage to it. Scale build up is caused by hard
water set at a high temperature.
Rinnai oers Southeastern Filtraon’s “ScaleCuer
Water Condioning System” that oers superior lime
scale prevenon and corrosion control by feeding a
blend of control compounds into the cold water
supply.
You must ensure that clearances will be met and that
the vent length will be within required limits. Consider
the installaon environment, water quality, and need
for freeze protecon. Requirements for the gas line,
water lines, electrical connecon, and condensate
disposal can be found in their respecve installaon
secons of this manual.
Part Number Descripon
103000038
Southeastern Filtratrion
ScaleCuer System 3/4” Feed
103000039
ScaleCuer Rell