34 Value Series Manual
Diagnosc Codes and Remedies
Some of the checks below should be done by a licensed professional. Consumers
should never aempt any acon that they are not qualied to perform.
WARNING
Code Denion Remedy
03 Power interrupon during Bath
Fill (Water will not ow when
power returns).
Turn o all hot water taps. Press ON/OFF twice.
10 Air Supply or Exhaust Blockage
Check that nothing is blocking the ue inlet or exhaust.
Check all vent components for proper connecons.
licensed
professional
only
Ensure approved venng materials are being used.
Ensure vent length is within limits.
Verify dip switches are set properly.
Check fan for blockage.
11 No Ignion
(heater not turning on)
Check that the gas is turned on at the water heater, gas meter, or cylinder.
If the system is propane, make sure that gas is in the tank.
Ensure appliance is properly grounded.
licensed
professional
only
Ensure gas type and pressure is correct.
Ensure gas line, meter, and/or regulator is sized properly.
Bleed all air from gas lines.
Verify dip switches are set properly.
Ensure igniter is operaonal.
Check igniter wiring harness for damage.
Check gas solenoid valves for open or short circuits.
Remove burner cover and ensure all burners are properly seated.
Remove burner plate and inspect burner surface for condensaon or debris.
Check the ground wire for the PC board.
12 No Flame
Check that the gas is turned on at the water heater, gas meter, or cylinder.
Check for obstrucons in the ue outlet.
If the system is propane, make sure that gas is in the tank.
licensed
professional
only
Ensure gas line, meter, and/or regulator is sized properly.
Ensure gas type and pressure is correct.
Bleed all air from gas lines.
Ensure proper venng material was installed.
Ensure condensaon collar was installed properly.
Ensure vent length is within limits.
Verify dip switches are set properly.
Check power supply for loose connecons.
Check power supply for proper voltage and voltage drops.
Ensure ame rod wire is connected.
Check ame rod for carbon build-up.
Disconnect and reconnect all wiring harnesses on unit and PC board.
Check for DC shorts at components.
Check gas solenoid valves for open or short circuits.
Remove burner plate and inspect burner surface for condensaon or debris.
14 Thermal Fuse has acvated
Check for restricons in air ow around unit and vent terminal.
licensed
professional
only
Ensure SW 5 in DIPSW 2 is in the o posion.
Check gas type of unit and ensure it matches gas type being used.
Check for low water ow in a circulang system causing short-cycling.
Ensure dip switches are set to the proper posion.
Check for foreign materials in combuson chamber and/or exhaust piping.
Check heat exchanger for cracks and/or separaons.
Check heat exchanger surface for hot spots which indicate blockage due to scale
build-up. Refer to instrucons in manual for ushing heat exchanger. Hard water
must be treated to prevent scale build up or damage to the heat exchanger.
Measure resistance of safety circuit.
Ensure high re and low re manifold pressure is correct.
Check for improper conversion of product.
16 Over Temperature Warning
(safety shutdown because unit is
too hot)
Check for restricons in air ow around unit and vent terminal.
licensed
professional
only
Check for low water ow in a circulang system causing short-cycling.
Check for foreign materials in combuson chamber and/or exhaust piping.
Check for blockage in the heat exchanger.