Loading ...
Loading ...
Loading ...
12
INTRODUCTION PRE-INSTALL NETWORKWIRING ACCESS CONTROL INSTALL
Admin Mode
Wiring REX (Request-to-Exit) and
Doors/LiftMaster Gate Operators
1. Connect a laptop to the CAP2D ADMIN USB port on the unit using a standard USB Mini-B cable.
a. The CAP2D ADMIN port is a USB interface for connecting the CAP2D unit to a laptop or PC to gain access to the local
administrative interface for debug and manual confi guration utilities.
b. The port requires a USB Mini-B cable for access between the laptop and the CAP2D unit.
1. Wire the REX and DOOR terminal block.
a. Connect the Normally Open (NO) contacts of the REX device to the REX and
COM terminals. Enable Request to Exit settings in myQbusiness.com Door
settings tab. Select State [x] NO (Normally Open).
When the switch closes, it initiates a Request-to-Exit (REX) program
sequence, including the option to activate the door or other relays, fi re and
door strike, and suppress any “Door Forced” messages.
b. Connect the Normally Closed (NC) contacts of the Door Sensor to the COM
and CONTACT terminals. Enable Request to Exit settings in myQbusiness.
com Door settings tab. Select State [x] NC (Normally Closed).
In this context, an NC switch is considered closed when the door is closed
(magnet present), and open when the door is open (no magnet is present).
When the switch is open, the control panel interprets this input as a “Door
Open” condition. When the switch is closed, the control panel interprets
this input as a “Door Closed” condition.
This circuit provides door status information (open/closed) to the control
panel so myQ
®
Business™ can take appropriate action locally, or send
email notifi cations if necessary.
2. Wire the DOOR LOCK RELAY terminal block.
a. Connect the door latch to the COM terminal and either the NO or NC terminal.
b. The DOOR LOCK RELAY provides both NO (Normally Open) and NC
(Normally Closed) contacts, and is driven in response to the presentation of
valid credentials or the programmable REX input.
c. Timing and other aspects of relay activation are programmed through myQ
®
Business™.
3. If used for an alarm shunt, wire the AUX RELAY 1 terminal block. If not used for
an alarm shunt, AUX RELAY 1 can be used for a variety of purposes. Enable [x]
Use Aux Relay setting in myQbusiness.com Door settings tab.
4. Wire AUX RELAY 2. Like the AUX RELAY 1, this terminal block can be used for a
variety of purposes. Enable [x] Use Aux Relay setting in myQbusiness.com Door
settings tab.
NOTE: The fully programmable AUX RELAYs provide both NO (Normally Open) and
NC (Normally Closed) contacts.
There is a 3 AMP 24 Volt DC limit on
through current for ALL relays.
Loading ...
Loading ...
Loading ...