Richmond 6RHE50 - 40,000 BTU Natural Gas Water Heater

User Manual - Page 11

For 6RHE50.

PDF File Manual, 40 pages, Read Online | Download pdf file

6RHE50 photo
Loading ...
Loading ...
Loading ...
11
WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type
shown on the rating plate. Such conversion could result in hazardous operating conditions.
Pressure Testing the Gas Supply System
The water heater and its manual gas
shut-off valve must be disconnected from
the gas supply piping system during any
pressure testing of that system at
pressures in excess of 1/2 psi (14” w.c.).
The water heater must be isolated from
the gas piping system by closing the
manual gas shut-off valve during any
pressure testing of the gas supply piping
at pressures equal to or less than
1/2 psi (14” w.c.).
Gas Supply
The branch gas supply line to the water
heater should be a clean 1/2” black
steel pipe or other approved gas piping
material.
A ground joint union or ANSI design
certified semi-rigid or flexible gas
appliance connector should be installed
in the gas line close to the water heater.
The National Fuel Gas Code (NFGC)
mandates a manual gas shut-off valve: See
(NFGC) for complete instructions.
If flexible connectors are used, the
maximum length shall not exceed 36”
and must meet the requirements in ANSI
Z21.24-Connectors for Gas Appliances.
If lever type gas shut-offs are used,
they shall be T-Handle type.
Compound used on the threaded joints of
the gas piping must be of the type resistant
to the action of LP gas. Use compound
sparingly on male threads only.
Where a sediment trap is not incorporated
as part of the appliance, a sediment
trap shall be installed downstream of
the equipment shutoff valve as close to
the inlet of the appliance as practical at
the time the appliance installation. The
sediment trap shall be either a tee fitting
with a capped nipple in the bottom outlet
or other device recognized as an effective
sediment trap.
Do not use excessive force (over 31.5 ft
lbs.) in tightening the pipe joint at the gas
control (thermostat) inlet, particularly if
teflon pipe compound is used, as the valve
body may be damaged.
The minimum inlet gas pressure (with
main burner on) to the water heater must
be a minimum of 5” w.c. for natural
gas, and a minimum of 11” w.c. for LP
gas. The maximum inlet pressure to the
water heater must not exceed 14" w.c. for
natural gas and LP gas. For purposes of
input adjustment, the minimum inlet gas
pressure (with main burner on) is shown
on the water heater rating plate. If high or
low gas pressures are present, contact your
gas supplier for correction.
Leak Testing
The water heater and its gas connections
must be leak tested at normal operating
pressures before it is placed in operation.
Turn on the manual gas shut-off
valve near the water heater.
Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must
be corrected.
The factory connections to the gas
control (thermostat) should also be leak
tested after the water heater is placed in
operation.
WARNING: Never use
an open flame to test for
gas leaks, as property
damage, personal injury, or
death could result.