Troubleshooting (continued)
Display
Condition Diagnostics Corrective Action(s)
TEMPERATURE
SENSOR
Occurs if a temperature
sensor has electrically
TIPSUFE4)035PSIBT
become disconnected
(OPEN).
Will automatically reset if the
condition clears.
Check all the temperature readings of the boiler on the DIAGNOSTICS -
5&.1&3"563&4NFOVUPEFUFSNJOFJGBOZTFOTPSTBSFDVSSFOUMZEJTQMBZFE
BT4)035PS01&/$PNQBSFUIJTUPUIFCPJMFSUFNQFSBUVSFTSFDPSEFE
JOUIF%*"(/045*$4&33034-0$,065)*4503:5&.1&3"563&4
during the last several lockout conditions.
Determine which sensors are suspect and measure their resistance
value and compare it to the values shown in 'JHVSFQBHF. If the
resistance values are incorrect replace the temperature sensor. Refer to
repair parts section for proper part number.
065%0035&.1JTUIFPQUJPOBMPVUEPPSBJSUFNQFSBUVSFTFOTPS*GUIJT
is not being used it will always be shown as NONE. This is normal unless
the sensors were installed.
Check wire harness for loose connections and pin engagement at sensor
DPOOFDUJPOBOEUIFDPOUSPMNPEVMF6OQMVHDPOOFDUJPOBUTFOTPSBOE
at control module and check continuity between ends.
If problem persists after checking items above replace control module.
Refer to repair parts section for kit number.
Occurs if dual temperature
sensors values have spread
by more that 10º F if the
burner is on.
Automatically resets when
sensors are within 10º F.
'PMMPXQSPDFEVSFBCPWFGPS4)035BOE01&/TFOTPSDPOEJUJPOTUP
properly diagnose sensor. If measured resistance values of sensors
convert to temperatures separated by more than 10º F replace the
sensor.
FLUE TEMP
TOO HIGH
Occurs if flue temperature
sensor exceeds 216º F.
Automatic reset occurs if
temperature drops below 216º F
for 2.5 minutes.
Manual reset is required if the
UFNQFSBUVSFSJTFTBCPWF¡'
Reset using manual reset screen
on display.
'PMMPXQSPDFEVSFGPSBCPWFGPS4)035BOE01&/TFOTPSDPOEJUJPOT
to properly diagnose sensor. In addition inspect heat exchanger
combustion chamber and flueways for abnormal wear or buildup.
Inspect vent system for abnormal wear or damage.
Contact Weil-McLain Technical Support.
LOW WTR
CUTOFF OPEN
Occurs if low water cutoff
contacts open.
Automatic reset occurs if contacts
are open at least one second, but
less than 5 seconds.
Manual reset of control module
if contacts are open longer than
5 seconds.
Check for low water condition in system. Repair system as necessary
refer to piping section of this manual.
If low water condition does not exist, check Diagnostics — Inputs screen
to view status of Low Water Cutoff. If shown as OPEN check wiring
b
etween LWCO and control module. If wiring is correct and functioning,
then replace the LWCO.
If LWCO option is not installed, check the wiring of the jumper in control
module’s plug P12.
DISPLAY COMM
Occurs if display
communications out for 30
seconds.
Automatically resets when
communication is re-established.
Check for a loose connection at the molex plug on the control and
connection on the back of the display.
LIMIT OPEN
Occurs if manual or
automatic r eset l imit op ens.
Automatic external limit will reset
2½ minutes after external limit
device closes.
Manual limit fault must be reset
using manual Reset screen on the
display.
Is there an external safety device connected? If yes, trouble shoot the
external limit to determine and correct the cause that opened the limit.
Also check for loose wiring connections.
Inspect the connector on control module’s plug P13.
Ensure a jumper is installed across the left two (Pins 1&2) terminals if not
using a manual reset external limit.
Ensure a jumper is installed across the right two (Pins 3&4) terminals if
not using an automatic reset external limit.
Troubleshooting (continued)
&IGURE Troubleshooting suggestions for %#/ boilers — &AULTDISPLAYSDIAGNOSTICSANDCORRECTIVEACTIONS
Part number 550-142-122/0513
95