Venting & air — general (cont.)
&IGURE Vent and air piping materials — Use only the materials listed below, ensuring that all materials meet
local codes (see Figure 109, page 107 for part/kit numbers)
)TEM Material
3TANDARDSFORINSTALLATIONSIN
5NITED3TATES #ANADA
(Note 2)
0LASTICPIPINGMATERIALS 6ENTORAIRPIPING 6ENTPIPING !IRPIPING
6ENTORAIRPIPE
lTTINGS
PVC schedule 40 ANSI/ASTM D1785 ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
PVC-DWV schedule 40 (Note 1) ANSI/ASTM D2665 NA
CPVC schedule 40 (Note 1) ANSI/ASTM F441 ULC S636
06#!"3PIPE
CEMENTPRIMER
PVC ANSI/ASTM D2564/F656 ULC S636
Use only cement
and primer
suitable for piping
material used
CPVC (Note 1) ANSI/ASTM F493 ULC S636
0OLYPROPYLENE
VENTPIPElTTINGS
TERMINATIONSAND
CEMENT
3IMPSON$URAVENTObtain all materials from M&G
Simpson-Duravent
#ENTROTHERM%CO3YSTEMS)NNO&LUE§3INGLEWALL
Obtain all materials from Centrotherm
See manufacturer’s literature for
detailed information
MUST USE LOCKING
COLLAR ON EVERY JOINT
ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
!,#STAINLESSSTEELPIPINGMATERIALS
6ENTPIPE
!,#
stainless
steel
Heat Fab, Inc. — Saf-T-Vent
®
Z-Flex, Inc. — Z-Vent II
Dura-Vent — FasNSeal™
Metal-Fab, Inc. — CORR/GUARD
Centrotherm Eco Systems — InnoFlue®
Certified for Category IV and
direct vent appliance venting
Certified for Category IV and direct vent
appliance venting
7EIL-C,AINSTAINLESSSTEELBIRDSCREENSvORv(purchase separately) — see Figure 109, page 107 for part numbers
Note 1: Weil-McLain concentric vent kits are made from PVC pipe
and ttings.
Note 2: System 636 PVC concentric terminations utilize PVC
pipe/ttings certied to ULC S636.
If ULC S636 compliance is required, use only System
636 pipe, ttings and cement.
DO NOT mix piping from dierent pipe manufacturers
unless using adapters specically designed for the pur-
pose by the manufacturer.
Every joint on polypropylene vent piping must in-
clude a locking collar.
DO NOT use cellular core PVC (ASTM F891), cellular
core CPVC, or Radel
®
(polyphenolsulfone) in venting
systems.
DO NOT cover non-metallic vent pipe and ttings with
thermal insulation.
ADAPTERS — AL29-4C piping — Install a PVC-to-stainless
adapter supplied by the AL29-4C stainless pipe manu-
facturer at the 3” PVC boiler vent connection and at the
termination (if using Weil-McLain plate or concentric PVC
termination).
ADAPTERS — Polypropylene piping — Provide adapters
from polypropylene pipe to the 3” PVC connections at
the boiler and at terminations, if required (Weil-McLain
sidewall plate, for example).
ADAPTERS — If using 2” piping, where approved for the
application, provide adapters for the 3” PVC boiler con-
nections and at the terminations, if required (Weil-McLain
sidewall plate, for example)
ALL vent and air pipes require a BIRD SCREEN at each termination. Most kits do not include
the bird screens. Purchase bird screens separately from Weil-McLain or vent kit supplier if
not included. [Note — bird screening is integral to the 3” PVC Weil-McLain sidewall vent
cap,
available for purchase from Weil-McLain
. No additional screening is required.]
USE SWEEP ELBOWS FOR ALL VENT AND AIR PIPING — DO NOT use short
radius elbows for vent or air piping. Boiler performance could be aected.
Part number 550-142-122/0513