Element Tag: <accydetect>
Attribute: “id” Accessory port number
Content 0 | 1 0 = Connector was disconnected
1 = Connector was connected
Example: <accydetect Sensed that a connector was plugged into accessory port 1
id=”1”>1</accydetect>
Accessory Port Jack Sensed
An Accessory Port Jack Sensed event is posted when a connecter is inserted into or removed from an accessory port input jack.
Element Tag: <accy>
Attribute: “id” Accessory port number
Content 0 | 1 0 = Condition sensed ON->OFF
1 = Condition sensed OFF->ON
Example: <accy id=”2”>1</accy> Accessory port 2 sense condition OFF->ON
Accessory Port Status
An Accessory Port Status event is posted when the connected sensor sense condition changes.
Element Tag: <set>
Attribute: None
Content <delay>…</delay> See Settings Event section for details
Example: <set>
<delay id=”1” act=”2”>12</delay> Outlet bank 1-power cycle delay=12 sec
</set>
Settings Changed
A Settings Changed event is posted when the device settings such as outlet bank delays, outlet bank trigger enable and display brightness is changed. Information for all
settings is transmitted, not just for the individual settings that changed.
Element Tag: <wiringfault>
Attribute: None
Content 0 | 1 0 = no wiring fault detected
1 = wiring fault detected
Example: <wiringfault>1</wiringfault> Wiring fault detected
Wiring Fault
A Wiring Fault event is posted when a change to the outlet wiring condition is detected.
Element Tag: <powercond>
Attribute: None
Content 0 | 1 | 2 | 3 0 = power normal
1 = fault recovery
2 = under voltage
3 = over voltage
Example: <powercond>3</powercond> Overvoltage condition
Power Condition
A Power Condition event is posted when the unit enters or recovers from over-voltage or under-voltage shutdown mode.