6
Fig.5-8
A Refrigerant pipe and insulating material
(Procurelocally)
B Pipecover(large)(Accessory)
C Pipecover(small)(Accessory)
D Refrigerantpipe(gas)
E Refrigerantpipe(liquid)
F Band(Accessory)
G Cross-sectionalviewofconnection
H Refrigerant pipe
I Insulating material
J Squeeze
J
H
I
B,C
F
G
A
F
F
B
D
E
C
5. Refrigerantpipingwork
5.4. Refrigerantanddrainagepipinglocations(Fig.5-7)
A Drain pipe
B Ceiling
C Grille
D Refrigerantpipe(liquid)
E Refrigerantpipe(gas)
F Mainunit
Model
Dimension(mm,inch)
A(liquid) B(gas)
SLZ-KF09
SLZ-KF12
63,2-15/32 72,2-27/32
SLZ-KF15
SLZ-KF18
63,2-15/32 78,3-1/16
5.5. Pipeconnection(Fig.5-8)
Indoorunit
1) Whenusingcommerciallyavailablecopperpipes:
• Applythinlayerofrefrigerantoiltopipeandjointseatingsurfacebeforetightening
arenut.
• Usetwowrenchestotightenpipingconnections.
• Air-purgetherefrigerantpipingusingyourownrefrigerantgas(don’tair-purgethe
refrigerantchargedintheoutdoorunit).
• Use leak detectoror soapy water to check for gas leaks after connections are
completed.
• Usearednutinstalledtothisindoorunit.
• Incaseofreconnectingtherefrigerantpipesafterdetaching,makethearedpart
ofpipere-fabricated.
• Userefrigerantpipinginsulationprovidedtoinsulateindoorunitconnections.Insulate
carefully following shown below.
2) Heatinsulationforrefrigerantpipes:
1 Wraptheenclosedlarge-sizedpipecoveraroundthegaspipe,makingsurethat
theendofthepipecovertouchesthesideoftheunit.
2 Wraptheenclosedsmall-sizedpipecoveraroundtheliquidpipe,makingsurethat
theendofthepipecovertouchesthesideoftheunit.
3 Securebothendsofeachpipecoverwiththeenclosedbands.(Attachthebands
20mm(25/32inch)fromtheendsofthepipecover.)
Makesurethattheslitinthepipecoverisfacingupwardwhenitisinstalled.
Seethatstopvalveonoutdoorunitisfullyshut(unitisshippedwithvalveshut).After
allpipingconnectionsbetweenindoorandoutdoorunithavebeencompleted,vacuum-
purgeairfromsystemthroughtheserviceportforthestopvalveontheoutdoorunit.
Aftercompletingproceduresabove,openoutdoorunitstopvalvesstemfully.This
completes connection of refrigerant circuit between indoor and outdoor units. Stop
valveinstructionsaremarkedonoutdoorunit.
Flarenuttightening
• Applyathincoatofrefrigerationoilontheseatsurfaceofpipe.(Fig.5-9)
• Forconnectionrstalignthecenter,thentightentherst3to4turnsofarenut.
• Usetightening torque tablebelowas aguidelinefor indoor unitsideunion joint
section,andtightenusingtwowrenches.Excessivetighteningdamagestheare
section.
AApplyrefrigeratingmachineoilovertheentireareseatsurface.
BUsecorrectarenutsmeetingthepipesizeoftheoutdoorunit.
CFlarenuttighteningtorque
Copper pipe O.D.
(mm,inch)
Flare nut O.D.
(mm,inch)
Tighteningtorque
(N·m,ft·lbs)
ø6.35,1/4 17,21/32 14to18,10to13
ø9.52,3/8 22,7/8 34to42,25to31
ø12.7,1/2 26,1-1/32 49to61,36to45
Fig.5-7
3-1/16(gas)
2-15/32(liquid)
(inch)
1/4 7-23/32 7-23/32
7-13/32
5-1/4 2-23/32
A
C
E
D
B
2-17/32
F
Fig.5-9
A
B
C