12
7. Electricalwork
Functiontable
Selectunitnumber00[table1]
Mode Settings Modeno. Setting no.
Initial set-
ting
setting
Powerfailureautomaticrecovery Notavailable
01
1
Available *1 2 Ο
*2
Indoor temperature detecting Indoorunitoperatingaverage
02
1 Ο
Setbyindoorunit’sremotecontroller 2
Remotecontroller’sinternalsensor 3
Selectunitnumbers01to03orallunits(AL[wiredremotecontroller]/07[wirelessremotecontroller])
Mode Settings Modeno. Setting no.
Initial set-
ting
setting
Filter sign 100Hr
07
1
2500Hr 2 Ο
Noltersignindicator 3
Fan speed Silent
08
1
Standard 2 Ο
High ceiling 3
Up/downvanesetting Not setting
11
1
Draftlesssetting(vanesanglesetup1)
2
Downwardsetting(vanesanglesetup2)
3 Ο
3Di-Seesensorpositioning*3
Position1 (""stampposition,page18)
12
1
(Position1)
2
Position3 ("○"stampposition,page18)
3 Ο
Fan speed during the cooling thermostat is OFF Setting fan speed
27
1 Ο
Stop
2
Extralow
3
*1Whenthepowersupplyreturns,theairconditionerwillstart3minutesor1minutelater(hingeonOutdoorunit).
*2Powerfailureautomaticrecoveryinitialsettingdependsontheconnectingoutdoorunit.
*3Whenthe3Di-Seesensorcornerpanelpositionchanged,changethismode.Refertopage18.
7.4.3.Howtosetthexedup/downairdirection
• Onlytheparticularoutletcanbexedtocertaindirectionwiththeproceduresbelow.
Oncexed,onlythesetoutletisxedeverytimeairconditioneristurnedon.(Other
outletsfollowUP/DOWNairdirectionsettingoftheremotecontroller.)
Explanationofword
• "RefrigerantaddressNo."and"UnitNo."arethenumbersgiventoeachaircondi-
tioner.
• "OutletNo."isthenumbergiventoeachoutletofairconditioner.
(Refertotheright.)
• "Up/Downairdirection"isthedirection(angle)tox.
Reset 1
horizontal
2 3 4 5
Electriccomponentbox
Outlet No. 1
Outlet No. 3 Outlet No. 2
Outlet No. 4
Horizontalairow
Remote controller setting
Theairowdirectionofthisoutlet
iscontrolledbytheairowdirec-
tion setting of remote controller.
Fixedsetting
Theairowdirectionofthisoutletisxed
in particular direction.
* Whenitiscoldbecauseofdirect
airow,theairowdirectioncanbexed
horizontallytoavoiddirectairow.
Downward
Note:
TheoutletNo. is indicatedbythe number of groovesonboth ends of each
airoutlet.Set theairdirectionwhilecheckingtheinformationshown onthe
remotecontrollerdisplay.
Airoutletidenticationmarks
Loading ...