Installation Manual - Page 13

For 3U24GS1ERE. Also, The document are for others Haier models: 2U18MS2VHB, 3U24MS2VHB, 4U36MS2VHB, AB09SC2VH*, AB12SC2VH*, AB18SC2VH*, AW07LC2VH*, AW09LC2VH*, AW12LC2VH*, AW18LC2VH*, AD07SL2VH*, AD09SL2VH*, AD12SL2VH*, AD18SL2VH*

Loading ...
Loading ...
Loading ...
INSTALLATION
PAGE 13
ENGLISH
Seacoast Application
Outdoor Unit Installation Complete
 The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If
the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the
installation instruction below.
ODU
ODU
Sea breeze
Sea
ODU
Sea breeze
Sea
ODU
Sea breeze
Sea
Protecti on walls
ODU
 Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage
the outdoor unit.
 If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the sea breeze.
 A protection wall should be constructed with a solid material such as
concrete to block the sea breeze and the height and the width of the wall
should be 1.5 times larger than the size of the outdoor unit. Also, secure
over 28 in (700mm) between the protection wall and the outdoor unit for
exhausted air to ventilate.
 Install the outdoor unit in a place where water can drain smoothly.
 
dust on the outdoor unit heat exchanger.